Eaton BladeUPS User Manual page 101

For use with eaton bladeups 5 kva to 60 kva (n+1) systems
Hide thumbs Also See for BladeUPS:
Table of Contents

Advertisement

Table 12. User Settings (Continued)
Description
Serial Port Config
Parallel Operation Settings
Battery Setup
Power Strategy
Start Screen
User Password
Audible Alarms
Unsynchronized Transfer to
Bypass
Transfer to Bypass hen
Overload
Automatic Start Delay
Control Commands from X-Slot1
Control Commands from
X-Slot2/Serv
X-Slot Signal Input Activation
Delay
Site
iring Fault Notice
Input Range
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 9 www.eaton.com/powerquality
Available Settings
Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
Parallel Operation Mode:
[Redundant Mode] [Capacity Mode]
This setting is not available for six-unit systems (must be
Redundant Mode only).
Parallel XCP: [System] [Sub Unit]
Select Sub Unit for PowerVision
®
software. Select System for
other software.
Auto ID Restart: [Done] [Restart]
Select Restart to reinitialize auto identification (see
"Auto-Identification" on page 117).
Number of EBMs: [0 through 4]
(See "Configuring the UPS for EBMs" on page 104.)
Battery Low Alarm Level: [1.750 through 1.950 volts per cell]
(See "Setting the Battery Low Alarm Level" on page 104.)
Automatic Battery Tests: [Enabled] [Disabled]
(See "Running Automatic Battery Tests" on page 105.)
External Battery Capacity: Set atts per cell
(See "Configuring the UPS for Customer-Supplied External
Batteries" on page 103.)
Use this setting only with customer-supplied external batteries
and the External Battery Interconnect.
[High Efficiency] [Standard]
For more information, see the following section, "Operating
Modes" on page 97.
Eaton logo
Mimic screen (see Figure 70 on page 93)
[Enabled] [Disabled]
If Enabled is selected, the password is USER.
[Normal Sound] [Disabled]
[Allowed] [Not Allowed]
[After a delay] [Immediately]
-1 through 32767 seconds
(-1 means disabled)
[Allowed] [Disabled]
Selecting Disabled prevents load commands such as Load Off
through the X-Slot, including remotely.
0 through 65 seconds
[Enabled] [Disabled]
[Standard] [ITIC}
Operation
Default Setting
19200
Redundant Mode
System
None
0
(means internal batteries only)
1.880 V/cell
(provides approximately 2.5 min
warning for the UPS)
Enabled
(automatically runs the battery test
once a month)
None
High Efficiency
Eaton logo
Disabled
Normal Sound
Not Allowed
After a delay
0s
Allowed
5s
Alarm Enabled
Standard
96