Standalone Ups Shutdown; Individual Paralleled Ups Shutdown - Eaton BladeUPS User Manual

For use with eaton bladeups 5 kva to 60 kva (n+1) systems
Hide thumbs Also See for BladeUPS:
Table of Contents

Advertisement

7 .
Check the UPS front panel display for active alarms or notices (other than "Batteries Disconnected").
Resolve any active alarms before continuing (see "Troubleshooting" on page 135.)
8.
Switch the UPS battery circuit breaker to the ON (
9.
If optional EBMs are installed, switch all EBM battery circuit breakers to the ON (
10. Verify that the "Batteries Disconnected" alarm has cleared. Verify that no other alarms appear on the UPS
front panel display.
If the
indicator is flashing, do not proceed until all alarms are clear. Check the UPS status from the
front panel to view the active alarms. Correct the alarms and restart if necessary.
11. Press any button on the front panel display to activate the menu options. Select CONTROL and GO TO
BYPASS MODE.
The
indicator illuminates solid and the
mode. The load is now powered by utility power.
If the
indicator is flashing, do not proceed until all alarms are clear. Check the UPS status from the
front panel to view the active alarms. Correct the alarms and restart if necessary.
12. Switch the load connector circuit breaker to the ON (
ESC
13. Press the
button until the Start screen appears.

Standalone UPS Shutdown

To shut down a standalone UPS (see Figure 60 on page 74):
1.
Switch the load connector circuit breaker to the OFF (O) position.
NOTE
The load connector breaker controls the load connector only, not the output power
cord.
2.
Press any button on the front panel display to activate the menu options. Select TURN UPS ON/OFF ,
TURN UPS OFF , and press the
3.
Confirm the selection. Press and hold the
The output relays open, the UPS transfers to Standby mode, and the
4.
Switch the UPS battery circuit breaker to the OFF (O) position.
5.
If optional EBMs are installed, switch all EBM battery circuit breakers to the OFF (O) position.
6.
Switch the UPS input circuit breaker to the OFF (O) position.
7 .
Switch off utility power where the UPS is connected.

Individual Paralleled UPS Shutdown

To shut down an individual UPS in the parallel system (see Figure 60 on page 74):
1.
Switch the load connector circuit breaker to the OFF (O) position.
NOTE
The load connector breaker controls the load connector only, not the output power
cord.
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 9 www.eaton.com/powerquality

) position.
indicator flashes, indicating the UPS is operating in Bypass

) position.
button.
button for three seconds, until the UPS stops beeping.
Operation

) position.
indicator turns off.
101