Page 3
S S p p e e c c i i a a l l S S y y m m b b o o l l s s The following are examples of symbols used on the product to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Page 4
Battery Module provided with the UPS to maintain an identical level of performance and safety. If there are any questions, don’t hesitate to contact your local Eaton representative.For potential safety issue on defective UPS : DISCONNECT INTERNAL BATTERY for storage and transportation.
6.1 Equipment Care ............................25 6.2 Storing the Equipment ..........................25 6.3 When to Replace Batteries ........................25 6.4 Replacing Batteries ........................... 25 6.5 Replacing the UPS Equipped with a HotSwap MBP ..................28 Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Page 6
8.3 Weights and Dimensions ........................... 33 8.4 Electrical Input ............................34 8.5 Electrical Input Connections ........................35 8.6 Electrical Output ............................35 8.7 Electrical Output Connection........................36 8.8 Battery ..............................36 8.9 Environmental and Safety........................... 36 Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
E E n n d d o o f f l l i i f f e e Eaton Tripp Lite Series will process products at the end of their service life in compliance with local regulations. Eaton Tripp Lite Series works with companies in charge of collecting and eliminating our products at the end of their service life.
- causing hours of lost productivity and expensive repairs. With the Eaton Tripp Lite Series SmartPro, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Providing outstanding performance and reliability, the Eaton Tripp Lite Series SmartPro’s unique benefits include:...
SMART3000RM2U SMART3000RM2UN Description (EBM) Weights (lb / kg) Dimensions (inch / mm) D x W x H BP48VRM2U 61.3 / 27.8 17.6x17.2x3.4 / 448x438x85.5 BP72VRM2U 89.1 / 40.4 23.7x17.2x3.4 / 603x438x85.5 Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
O O p p t t i i o o n n a a l l a a c c c c e e s s s s o o r r i i e e s s Table 4. Smart Pro Optional Accessories Part number Description BP48VRM2U Extended Battery Module BP72VRM2U WEBCARDLXE UPS Web Management Accessory Card SNMP Remote Monitoring HTML5 Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
RPO ( Remote Power Off) Slot for optional communication card Connector for additional battery module Connector for automatic recognition of an additional battery module Ground screw SMART2200RM2U / SMART2200RM2UN SMART3000RM2U / SMART3000RM2UN BP48VRM2U / BP72VRM2U Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Page 12
Rear panel Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
15. RS232 communication cable 16. USB communication cable 17. Safety instructions 18. Quick start 20. Rack kit for 19-inch 4-post enclosures 21. Two supports for tower position (tower feet) WEBCARDLXE (optional) RESET CONFIG STATUS Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
NOTE The rails and necessary hardware are supplied by Eaton. I I n n s s t t a a l l l l a a t t i i o o n n i i n n t t o o w w e e r r p p o o s s i i t t i i o o n n If you ordered other UPS accessories, refer to specific user manuals to check the tower installation with the UPS.
Page 15
Recommended Positions Follow steps 1 to 5 to adjust the orientation of the LCD panel and of the logo. Figure 2. Tower Installation Steps Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
A small amount of arcing may occur when connecting the internal batteries. This is normal and will not harm personnel. Connect the cables quickly and firmly. Remove the front panel by pressing on both sides of the panel. Connect the two battery connectors together. Replace the front panel. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
E E B B M M C C o o n n n n e e c c t t i i o o n n The optional CBLADAPT48 or CBLADAPT72 cables are forbidden with Eaton Tripp Lite Series SmartPro models installed in the US or Canada.
U U P P S S c c o o n n n n e e c c t t i i o o n n Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source and the true electrical consumption of the total load. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
C C o o n n n n e e c c t t i i o o n n w w i i t t h h a a H H o o t t S S w w a a p p M M B B P P ( ( M M a a i i n n t t e e n n a a n n c c e e B B y y P P a a s s s s ) ) o o p p t t i i o o n n a a l l m m o o d d u u l l e e The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads (HotSwap function). Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
H H o o t t S S w w a a p p M M B B P P m m o o d d u u l l e e t t e e s s t t Set switch (45) to Bypass position and check that the load is still supplied. Set switch (45) back to Normal position. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
The second line shows measures. The backlight LCD automatically dims after 5 minutes of inactivity. Press any button to restore the screen. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
6th Screen: BAT: xx. xV xxx% percentage. Battery voltage and charge percentage Battery voltage:1 decimal. Charge percentage:0 decimal. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Page 23
1 beep every 3 seconds warning may occur before the battery reaches 20% capacity remaining. Some fault has happened to the UPS. Fault Mode See for additional information. Action may be needed. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
REMOTE PWR OFF Select input signal function for INPUT DB9-4. COM SETTING INPUT DB9-4 Select output signal function for OUTPUT RELAY. OUTPUT RELAY Select output signal function for OUTPUT DB9-1. OUTPUT DB9-1 Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Page 25
Select output signal function for OUTPUT DB9-7. OUTPUT DB9-7 Select output signal function for OUTPUT DB9-8. OUTPUT DB9-8 Event log has utmost 50 items to show what happened. EVENT LOG IDENTIFICATION This menu shows IDENTIFICATION information. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Page 26
Display Functions Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
To shut down the UPS: Press the button on the front panel for three seconds. The UPS starts to beep and shows a status of "SHUTTING DOWN...". The UPS then transfers to Standby mode. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
O O p p e e r r a a t t i i n n g g m m o o d d e e s s The Eaton Tripp Lite Series SmartPro front panel indicates the UPS status through the UPS indicators located above the LCD screen.
R R e e t t r r i i e e v v i i n n g g t t h h e e e e v v e e n n t t a a n n d d f f a a u u l l t t l l o o g g To retrieve the event and fault log through the display: Press any button to activate the menu options, then select event log. Scroll through the listed events and faults. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Page 30
Retrieving the event and fault log Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
If you store the equipment for a long period, recharge the battery every 6 months by connecting the UPS to utility power. The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton recommends that the batteries charge for 48 hours after long-term storage.
Page 32
Disconnect the battery pack by separating the connectors (never pull on the wires). Remove the metal protection cover in front of the battery (three screws). Pull the plastic tab to remove the battery pack and replace it. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Page 33
UPS is in Normal mode with no active alarms, and the bypass voltage is acceptable. During the battery test, the UPS transfers to Battery mode and discharges the batteries for 10 seconds. The front panel displays "BAT TESTING". Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
"UPS ON - OK to switch" on the HotSwap MBP module goes ON (otherwise, there is a connection error between the HotSwap MBP module and the UPS). Set switch (45) to Normal position. The red LED on the HotSwap MBP module goes OFF. Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Page 35
If the UPS. If the condition continues to persist, LED is On temperature rises another 10°C, the UPS contact your service representative. shuts down. 1 beep every 3 seconds Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Phase neutral inversion on single phase UPS #809 INDU OVERLOAD Inductive overload occurred, transfer to Fault mode #80A CAPA OVERLOAD Capacitive overload occurred, transfer to Fault mode #804 IMBALANCE LOAD Load is unbalance Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
S S e e r r v v i i c c e e a a n n d d S S u u p p p p o o r r t t If you have any question or problem with the UPS, call Eaton Tripp Lite Series or your local service representative in your country / region.
Service and Support Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Page 39
Description (UPS) Weights (lbs / kg) Dimensions (inch / mm) D x W x H SMART750RMXL2U 44.5 / 20.2 17.6x17.2x3.4 / 448x438x85.5 SMART750RMXL2UN 44.5 / 20.2 17.6x17.2x3.4 / 448x438x85.5 SMART1000RMXL2U SMART1000RMX2UN Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Model Current limitation battery mode 1000 1500 2200 3000 Transfer time Utility Outage: 1-4ms for normal mode, >5ms for sensitive mode Utility abnormal: <10ms for normal mode ,<25ms for sensitive mode Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Up to 3,000 meters (9,843 ft) above sea level, no derating for 40°c (104°F) room Operating altitude temperature Transit altitude Up to 10,000 meters (32,808 ft) above sea level Audible noise Line mode:<40dB Buck/boost mode:<45 dB Batt. Mode: <45dB, 50dB for 3K Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 03...
Need help?
Do you have a question about the Tripp Lite Series SmartPro Series and is the answer not in the manual?
Questions and answers