Eaton BladeUPS User Manual page 73

For use with eaton bladeups 5 kva to 60 kva (n+1) systems
Hide thumbs Also See for BladeUPS:
Table of Contents

Advertisement

Electronics Module
Locking crew
Figure 50. Removing the Electronics Module
11. If the mounting brackets are not already installed, align the two mounting brackets with the screw holes
on the sides of the UPS and secure with the supplied 6-32 flat-head screws (see Figure 51).
Figure 51. Installing the UPS Mounting Brackets
12. Slide the UPS into the rack.
13. Parallel or parallel-ready system only. If you are installing other X-Slot cards besides the Powerware Hot
Sync CAN Bridge Card, skip to Step 16.
NOTE
Leaving the UPS unattached allows you to adjust the UPS position in the rack for any
clearance needed to install the X-Slot cards.
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 9 www.eaton.com/powerquality
Ring Handle
Mounting Bracket
6-32 Flat-Head
crews
Standard System Installation
67