4.10.5 Output terminal function selection (Pr. 190 to Pr. 196)

You can change the functions of the open collector output terminal and relay output terminal.
Parameter
Number
RUN terminal
190
function selection
SU terminal function
191
selection
IPF terminal function
192
selection
OL terminal function
193
selection
FU terminal function
194
selection
ABC1 terminal
195
function selection
ABC2 terminal
196
function selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 156)
(1) Output signal list
⋅ You can set the functions of the output terminals.
⋅ Refer to the following table and set the parameters: (0 to 99: Positive logic, 100 to 199: Negative logic)
Setting
Signal
Positive
Negative
Name
Logic
Logic
0
100
RUN
Inverter running
1
101
SU
Instantaneous power
2
102
IPF
failure/undervoltage
3
103
OL
Overload alarm
Output frequency
4
104
FU
detection
5
105
FU2
7
107
RBP
8
108
THP
10
110
PU
PU operation mode
Inverter operation
11
111
RY
ready
Output current
12
112
Y12
detection
13
113
Y13
Initial
Name
Value
0
1
Open
collector
2
output
terminal
3
4
99
Relay
output
terminal
9999
Function
Output during operation when the inverter
output frequency rises to or above Pr. 13
Starting frequency.
Output when the output frequency is
Up to frequency
*1
reached to the set frequency.
Output at occurrence of an instantaneous
power failure or when undervoltage
protection is activated.
Output while stall prevention function is
activated.
Output when the output frequency reaches
the frequency setting in Pr. 42 (Pr. 43 for
reverse rotation).
Second output
Output when the output frequency reaches
frequency detection
the frequency setting in Pr. 50.
Output when 85% of the regenerative brake
Regenerative brake
duty set in Pr. 70 is reached.
prealarm
Setting can be made for the 75K or more.
Output when the electronic thermal relay
Electronic thermal
function cumulative value reaches 85%.
relay function
(Electronic thermal relay function protection
prealarm
(E.THT/E.THM) actirates, when the value
reached 100%.)
Output when the PU operation mode is selected.
Output when the inverter power is turned on,
then output after reset process is completed.
(when the inverter can be started by switching
the start signal on or while it is running).
Output when the output current is higher
than the Pr. 150 setting for longer than the
time set in Pr. 151.
Output when the output power is lower than
Zero current
the Pr. 152 setting for longer than the time
detection
set in Pr. 153.
Function assignment of external
Initial Signal
RUN (inverter running)
SU (up to frequency)
0 to 5, 7, 8, 10 to 19, 25, 26,
45 to 47, 64, 70, 90 to 96, 98, 99,
IPF (instantaneous power
100 to 105, 107, 108, 110 to 116,
failure, undervoltage)
125, 126, 145 to 147, 164, 170,
190 to 196, 198, 199, 9999
OL (overload alarm)
FU (output frequency
detection)
0 to 5, 7, 8, 10 to 19, 25, 26, 45 to
ALM (alarm output)
47, 64, 70, 90, 91, 94 to 96, 98, 99,
100 to 105, 107, 108, 110 to 116,
125, 126, 145 to 147, 164, 170,
No function
190, 191, 194 to 196, 198, 199,
9999
Operation
terminal and control
Setting Range
Related
Refer
Parameters
to Page
109
Pr. 41
111
Pr. 57
126
Pr. 22, Pr. 23,
Pr. 66, Pr. 148,
73
Pr. 149, Pr. 154
Pr. 42, Pr. 43
111
Pr. 50
111
Pr. 70
99
Pr. 9
96
Pr. 79
158
109
Pr. 150, Pr. 151
112
Pr. 152, Pr. 153
112
107
4