Installation and Setup

Site Recommendations

When placing the enclosure, follow the recommendations and precautions in this section to reduce
potential installation and operation hazards.
Environment
Chassis Accessibility
Make sure the front and rear panels of the enclosure are accessible, so that you can monitor the LED
indicators. Leaving adequate clearance at the rear will also allow for easier cabling and service.
Power
The source's electrical outlet should be installed near the router, easily accessible, and properly
grounded. Power should come from a building branch circuit. We recommend using a dedicated line
for the system's power. Use a minimum breaker current rating of 15 A for 110 V or 30 A for 230 V.
To avoid an overload, note the power consumption rating of all the equipment connected to the circuit
breaker before applying power.

General Hazard Precautions

These recommendations address potential hazards that are common to all installations:
Elevated Operating Temperature
The maximum rated ambient temperature for Modula enclosures is 110° F (43° C).
All equipment should be installed in an environment compatible with the manufacturer's maximum
rated ambient temperature. In a closed or multi-unit rack assembly, the operating ambient temperature
of the rack environment may be greater than the ambient room temperature.
Caution: To protect the equipment from overheating, do not operate in an area that exceeds
110° F (43° C) and follow the clearance recommendation below for adequate airflow.
Airflow Restriction
Modula enclosures are designed to adequately dissipate the heat they produce under normal operating
conditions; however, this design is defeated when high heat producing equipment is placed directly
above or below an enclosure.
Caution: To prevent overheating, avoid placing high heat producing equipment directly above
or below the enclosure. The system requires a minimum of one empty rack unit above and below
(three empty rack units are recommended). Verify that the openings on the sides of the enclosure
are not blocked and do not have restricted air flow.
Mechanical (Rack) Loading
When installing equipment in a rack, distribute the weight to avoid uneven mechanical loading.
Modula Instruction Manual
Choose a clean, dust free, (preferably) air-conditioned location.
Avoid areas with direct sunlight, heat sources, or high levels of EMI
(Electromagnetic Interference).
If applicable, to make control panel operations easier, mount the enclosure with the control
panel in the rack at eye level.