A Specifications; Power Requirements - HP D5970A - NetServer - LCII Installation Manual

Hp netserver lxr 8500 installation guide
Hide thumbs Also See for D5970A - NetServer - LCII:
Table of Contents

Advertisement

A Specifications

Power Requirements

Table A-1. Power Requirements
Voltage and frequency
Maximum continuous power
input
Operating Current
Maximum inrush current
Delayed action circuit breaker
recommended
Power availability
NOTE
Some local codes do allow a 16-amp device to be connected to
a 16-amp service. Consult a qualified electrician or local
regulatory authority before beginning electrical site
preparation.
200-240 VAC; 50/60 Hz
1100 W Maximum (8-CPU configuration)
5.6 AMPs Maximum at 200/208 Volts AC
4.9 AMPs Maximum at 230/240 Volts AC
150 AMPs for 4 ms
North America: a 20 A minimum circuit is to be
used with one NEMA AB1 class 14B breaker
for each 16 A power distribution unit (PDU) that
is connected to an HP NetServer LXr 8500.
Europe (single server in a rack): use a 16
A-minimum circuit with one IEC MCB C-type
breaker for each 16 AMP PDU.
Europe (multiple servers in a rack): use a
16-amp-minimum circuit with one IEC MCB
D-type breaker for each 16 AMP PDU.
1500 DC watts continuous (2 power supplies
minimum)
167

Advertisement

Table of Contents
loading

Table of Contents