How To Set The Constant Current Output - Fuji Electric FLR-3 Instruction Manual

Ultrasonic flowmeter m-flow pw flow transmitter
Table of Contents

Advertisement

4.11.2. How to set the constant current output

Description
 Generates a fixed value output of analog signal.
Application example: The operation of a connected receiver is checked by generating a fixed value output of analog signal.
 n the constant current setting mode (OUTPUT SETTING), set the constant current output value.
Settable range: -20%(0.8mA) to +120%(23.2mA)
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.4.1.)
Operation
Set the constant current output of 50% (12mA).
(example)
Key operation
Press the
Press the
ENT
Press the
Press the
ENT
Press the
ENT
Note) Start constant current output.
Enter "5" by the
Press the
ENT
Press the
ESC
Note) Current output is in the measurement status.
Press the
ESC
measurement mode.
- 62 -
Description
key for 4 times to display "MAINTENANCE MODE".
key once to display "RAS INFORMATION".
ENT
key twice to display "OUTPUT SETTING".
key once to display the setting screen.
ENT
key once to blink the cursor.
ENT
and the
key.
key once to output 12mA.
ENT
――― Outputting 12mA. ―――
key once to stop constant current output.
ESC
key once and then press the
ESC
MAINTENANCE MODE
RAS INFORMATION
0000000000000000
CURRENT
OUTPUT SETTING
OUTPUT SETTING
OUTPUT SETTING
OUTPUT SETTING
OUTPUT SETTING
CURRENT
key once to enter the
Display
OUTPUT SETTING
0 %
+000 %
+050 %
 COMPLETE 
50 %
OUTPUT SETTING
0.000
%
0.000
m3
INF-TN3FLR-E