3. SELECTION OF INSTALLATION PLACE
Select an installation place taking into account the following matters from the viewpoint of easiness of maintenance and
checkup, instrument life and securing the reliability.
(1) A place where ambient temperature and humidity are:
• –20 to 50 C and 90% RH or less for flow transmitter (FLR)
(2) A place not exposed to direct sunshine nor weathering.
(3) Sufficient space for daily inspection, wiring, etc.
(4) A place not subjected to radiated heat from a heating furnace, etc.
(5) A place not subjected to corrosive atmosphere.
(6) A place not to be submerged.
(7) A place free from excessive vibration, dust, dirt and moisture.
Secure at least 100 mm of space between the flow
transmitter and nearby wall. Also secure a space
of opening the front cover for maintenance.
Secure a cable wiring space under the case.
- 6 -
AUTION
3.1. Flow transmitter
133
133
370 min.
Top view of mounting
100
min.