Advertisement

4.10.7. Setting of the operation mode

Description
 Used to switch computation cycle and output cycle.
 Settable range
NORMAL
: Standard mode (factory-set value), computation/output cycle is approximately 0.5 seconds.
HIGH SPEED : High speed response mode, computation/output cycle is approximately 0.2 seconds.
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.4.1.)
Operation
Switch the operation mode to the high speed response mode.
(example)
Key operation
Press the
Press the
ENT
Press the
Press the
ENT
Press the
Press the
ENT
――― "OPERATION MODE" has been registered. ―――
Press the
ESC
the measurement mode.
Reference
The difference between standard mode and high speed mode
High speed mode is unfit for the measurement when foreign objects or air bubbles are contained.
Standard mode is about 10 times more resistant to entry of foreign objects or air bubbles than high speed mode.
- 60 -
Description
key twice to display "OUTPUT SETUP".
key once to display "ZERO ADJUSTMENT".
ENT
key for 10 times to display "OPERATION MODE".
key once to blink the cursor.
ENT
key for 6 times to move the cursor.
key once to register.
ENT
key once and then press the
ESC
OUTPUT SETUP
ZERO ADJUSTMENT
OPERATION MODE
OPERATION MODE
OPERATION MODE
OPERATION MODE
OPERATION MODE
key for 3 times to enter
Display
SET ZERO
NORMAL
NORMAL
HIGH SPEED
 COMPLETE 
HIGH SPEED
0.000
%
0.000
m3