Table 10. Smart DC Controller - Installer Menu Functions
Ref.
User Menu
No.
Display
SS 0 (OFF)
IES STOP ONLY
14
LC 0 (0.0 SECS)
LEAF DELAY CLOSE
15
LO 0 (0.0 SECS)
LEAF DELAY OPEN
16
RT 0 (60 SECS)
MAXIMUM RUN TIMER
17
PO 0 (OFF)
PARTIAL OPEN
18
EC 0 (STOP ONLY)
EYE CLOSE LOGIC
19
Setting Options
(Bold = Factory
Menu Tasks and Explanations
Settings)
In a Usage Class 4 environment,
0 = stop,
operator can be set to stop gate
reverse for 2s
and not reverse gate travel after
1 = stop only
an IES trip.
0 = no delay
Only appears if the gate operator is
1 through 20
set up as a Primary or a Secondary.
in ½ second
Available settings are 1 through
increments
20. Each increment adds ½ second
time delay following a command to
For example:
close before the operator activates.
1 = ½ second
Provides up to a 10 second time
10 = 5 seconds
delay.
20 = 10 seconds
0 = no delay
Only appears if the gate operator is
1 through 20
set up as a Primary or a Secondary.
in ½ second
Available settings are 1 through
increments
20. Each increment adds ½ second
time delay following a command to
For example:
open before the operator activates.
1 = ½ second
Provides up to a 10 second time
10 = 5 seconds
delay.
20 = 10 seconds
Doesn't appear in SlideSmart.
0 = 60 Seconds
Assigns a motor run time of 60 or
max run,
300 seconds. If the gate opening
or closure takes longer than 60
1 = 300 Seconds
seconds, you'll need to set the run
max run
timer to 1.
Sets distance (from closed gate
0 = OFF
position) where gate stops if the
partial open input is activated.
7 = 7 ft, 8 = 8ft,
When a number is entered in
through 32 = 32
PO display, open partial input
ft
becomes operational.
Default setting is non-reversal if
0 = Close eye
close photo eye is triggered while
stops only
closing. A setting of 1 causes gate
1 = 2s reverse to
to reverse toward open for two
open
seconds if triggered while closing.
A setting of 2 reverses the gate to
2 = Full Open
full open.
DISPLAY AND MENU OPTIONS
DC Controller
Display
Connections
(N/A)
DUAL GATE inputs
on both operators
DUAL GATE inputs
on both operators
(N/A)
OPEN PARTIAL COM
Sensor Common
Sensor Input
MX4505 Rev.H ©2022
65
65