PRIMARY AND SECONDARY MENU SETUP

Determine which unit will be set up as the Primary.
The other unit will be set up as the Secondary. It
doesn't matter which unit is which, but you must
identify the Primary and Secondary operators by
taking the following steps and Figure 64:
Start by configuring the PRIMARY unit.
1. At a gate status display, press the MENU
button twice. This accesses the User Menu and
the CLOSE TIMER display appears.
2. Simultaneously, press the OPEN and RESET
buttons to enter the Installer Menu. Release
the buttons and the LEARN LIMITS display
appears which is the first item in the Installer
Menu.
3. Press NEXT until the DUAL GATE display
appears. The factory default setting is 0.
4. Use the SELECT and NEXT buttons to navigate
and change the setting to 2 PRIMARY.
5. To exit the Installer Menu, press the MENU
button. A gate status appears in the display
indicating you have returned to Run Mode or
Error 4 will be shown if the secondary operator
is not programmed correctly or wiring is
wrong..
NOTICE
For proper operation, you must set the other
gate operator as SECONDARY.
6. Move to the other SlideSmart operator.
7. Using the buttons on the Smart DC Controller,
access the DUAL GATE display through the
Installer Menu.
8. Perform the same steps, 1 through 5, but
address the operator as SECONDARY, setting
1.
When the SlideSmart operator has been
designated as the primary and the other as
secondary, the dual-gate operators will be in
constant communication, most often, in a peer-
to-peer relationship. For example,
• Any control input that is attached to the
secondary unit will be recognized by the primary
BI - PARTING GATE SYSTEMS
once the Installer Menu is properly configured
in both units.
• A diagnostics log is maintained in each unit, but
both units run and store the errors codes and
diagnostics pertinent to each other.
• The primary unit controls the close timer even if
the timer is set in the slave unit. If a close timer
is set in both units, the primary unit overrides
the secondary setting.
NOTICE
If the dual-gate communication stops for
whatever reason, (communication wire severed
or the power switch is turned off in one unit),
both operators cease to function and an
ERROR 4 (Primary/Secondary Communication
Error) appears in the display.
HYSECURITY
GATE CLOSED
OPEN
CLOSE
STOP
MENU
RESET
SELECT
PREV
NEXT
CT 0 (OFF)
CLOSE TIMER
OPEN
CLOSE
STOP
MENU
PREV
NEXT
SELECT
LL 0 (OFF)
LEARN LIMIT
OPEN
CLOSE
STOP
MENU
PREV
NEXT
SELECT
DG 2 (MASTER)
DUAL GATE
OPEN
CLOSE
STOP
MENU
PREV
NEXT
SELECT
Figure 65. Primary-Secondary Menu Setup
1. Start at a gate
status display.
2. To access the
User Menu,
press the MENU
button twice.
RESET
3. Access the
Installer Menu, by
simultaneously,
pressing the
OPEN and
RESET
buttons.
RESET
4. Use NEXT to
navigate to the
menu display.
Change the
setting using the
SELECT and
NEXT buttons.
RESET
MX4505 Rev.H ©2022
87
87

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HySecurity SlideSmart DC Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents