Table 10. Smart DC Controller - Installer Menu Functions
Ref.
User Menu
No.
Display
S1 0
SENSOR #1 TYPE
25
S2 0
SENSOR #2 TYPE
26
S3 0
SENSOR #3 TYPE
27
DT 0 FREE EXIT
DISABLE FUNCTION
28
OR 1 REVERSE
OUTSIDE OBS LOOP
29
Setting Options
(Bold = Factory
Menu Tasks and Explanations
Settings)
0 - disabled
UL 325 - 2018 sensor input setting
1 - (NOT USED)
for external entrapment protection
sensor monitoring. All three sensor
2 - (EYE CLOSE)
inputs must be configured to a
3 - (EDGE CLOSE
non-zero number before the gate
operator will move the gate. Edge
4 - (EYE OPEN)
Both is only available in Swing Gate
5 - (EDGE OPEN)
operator types. Eye Both is only
available in Slide Gate operator
6 - (EDGE BOTH)
types.
7 - (EYE BOTH)
Same as Sensor 1 Same as Sensor 1
Same as Sensor 1 Same as Sensor 1
Configures BLOCK EXIT input to
disable either Free Exit Detector
function or, alternately, Close
0 = Disable Free
Timer function. Default setting
Exit
disables free exit detector.
1 = Disable
NOTE: Free exit is disabled when
Close Timer
gate is at its closed limit. If closed
limit is not tripped, free exit
continues to work normally.
Default is for full reversal when
0 = Pause closing
Outside Obstruction Loop is
only
triggered while closing. A setting
of 0 causes gate to only pause
1 = Enable
when triggered. Gate closure
reversing to
continues as soon as loop is clear
open
again.
DISPLAY AND MENU OPTIONS
DC Controller
Display
Connections
BLOCK EXIT COM
OUTSIDE OBS
LOOP COM or
Hy5B
MX4505 Rev.H ©2022
67
67