ENGLISH GENERAL SAFETY WARNINGS AND PRECAUTIONS Translation of the original instructions in full GENERAL SAFETY WARNINGS AND PRECAUTIONS 1.1 GENERAL WARNINGS Prior to installing the appliance, carefully read and CONTENTS observe these instructions, since incorrect installa- tion can cause serious harm to people and damage to the appliance.
INTENDED USE installation or incorrect balancing of the automation can lead to injuries. SO2000 is an electromechanical actuator for automating sec- PRODUCT DESCRIPTION AND INTENDED USE – The packing materials of the product must be disposed tional doors up to 20 m2. Thanks to the cable outlet shaft, it of in compliance with local regulations.
– the door dimensions must be below 20 m2 These indicators must be added together to obtain the overall – the drive shaft must be compatible with the SO2000 output severity index, which in this case is 60%. With the value iden- and the relative keys supplied with the package tified (60%), look at the horizontal axis of the graph (“severity...
3.3 PRODUCT IDENTIFICATION AND OVERALL Table 3 DIMENSIONS PRODUCT DURABILITY The overall dimensions and the label (A), which allows for iden- Severity index tifying the product, are shown in “Figure 3”. < 100 kg 100 - 180 kg Weight of the door 180 - 230 kg >...
3.5 PRE-INSTALLATION WORKS The figure shows an example of an automation system, constructed using Nice components. A Gearmotor Note 1 If the power supply cable is longer than 30 m, a cable B Photocells with larger cross-sectional area (3 x 2.5 mm...
(C) pro- vided SO2000 can be installed in the horizontal position using the release mechanism (F), supplied with the kit, which must be fastened with the three screws in the position shown, while making sure that the unlocking cables (G) are fed through.
insert all the connecting cables into the various devices, 3.7 MANUALLY UNLOCKING AND LOCKING THE leaving them 20–30 cm longer than necessary. Refer to “ GEARMOTOR Table 4” for the type of cables and to “Figure 5” for the The gearmotor is equipped with a mechanical unlocking device connections.
4.2 WIRING DIAGRAM AND DESCRIPTION OF CONNECTIONS 4.2.1 Wiring diagram IBT4N FUSE Close Open Stop Bluebus Flash FLASH Bluebus Bluebus AERIAL 4.2.2 Description of connections Table 5 ELECTRICAL CONNECTIONS Terminals Description This output is programmable (refer to the “PROGRAMMING” chapter) to connect one of the following devices: Warning light, “Door open indicator”...
ELECTRICAL CONNECTIONS Terminals Description This terminal can be used to connect compatible devices, which are all connected in parallel with only two wires carrying both the electric power and communication signals. BLUEBUS For further information on the BlueBUS, refer to the “Addressing of devices connected with the BlueBUS system”...
4.3.1 FT210B photosensor 5.2 DEVICE LEARNING The FT210B photosensor combines in a single device a force Once the power supply has been connected, the control unit limiting system (type C, in accordance with the EN12453 stand- must recognise the devices connected to the “BlueBUS” and ard) and a presence sensor that detects obstacles on the line “STOP”...
Page 12
The position memorisation procedures are described below. Position RINT programming, LED “L4” flashes: Two procedures are available: If the intermediate slowdown position does not have to be – FULL: enables the user to manually set multiple positions programmed, press the button twice rapidly to skip to (FCA-opening limit switch, RA-opening slowdown, RI-interme- the next programming;...
the courtesy light will start flashing once every second To do this: (1 Hz) to signal the need to run the MANDATORY “Auto- press the button to command an “Open” manoeuvre; matic Force Search” procedure. During the “Automatic check that the door opens properly without any speed Force Search”...
Commissioning can only be performed after all test- structions for all the automation’s devices. ing phases have been successfully completed. For all the above-mentioned documentation, Nice – through its technical assistance service – provides Before commissioning the automation, ensure that the following: pre-completed forms.
PROGRAMMING There are 3 buttons on the control unit: (“Figure PROGRAMMING 23”) which can be used both to command the control unit during the testing phase and to programme the available functions. FUSE L1 ... L8 The available programmable functions are grouped into two levels and their operating status is signalled by eight LEDs “L1 ...
7.2 LEVEL 1 PROGRAMMING (ON-OFF) All the Level 1 functions are factory-set to “OFF” and can be modified at any time. To check the various functions, refer to “Table 8”. 7.2.1 Level 1 programming procedure The user has maximum 10 seconds to press the buttons consecutively during the programming procedure, after which time the procedure terminates automatically and memorises the changes made up to then.
7.3 LEVEL 2 PROGRAMMING (ADJUSTABLE PARAMETERS) All the Level 2 parameters are factory-set as highlighted in “GREY” in “Table 9” and can be modified at any time. The parameters can be set to a scale of 1 to 8. The check the value corresponding to each LED, refer to “Table 9”. 7.3.1 Level 2 programming procedure The user has maximum 10 seconds to press the buttons consecutively during the programming procedure, after which time the procedure terminates automatically and memorises the changes made up to then.
Page 18
LEVEL 2 FUNCTIONS (ADJUSTABLE PARAMETERS) Entry LED Parameter LED (level) Set value Description Door Open Indicator Enabled if door closed Enabled if door open Warning light Selects the device connected to the L4** FLASH output FLASH output. Electric latch Electric lock Suction cup Maintenance indicator Force 1 (low)
7.4 PROGRAMMING THE DIRECTION 7.6 SPECIAL FUNCTIONS This procedure allows for reversing the motor’s rotation direc- tion. 7.6.1 “Always open” function To do this: The “Always open” function is a control unit feature that enables press and hold the button for roughly 3 seconds the user to always command an opening manoeuvre when the release the button when LED “L1”...
Table 10 MAINTENANCE NOTICE THROUGH FLASH AND MAINTENANCE INDICATOR Number of Maintenance Signal on “Flash” manoeuvres indicator signal FUSE Lit for 2 seconds Normal (0.5 sec on, Below 80% of the at the start of the 0.5 sec off) limit opening manoeuvre Remains lit for 2 Flashes for the...
TROUBLESHOOTING... (troubleshooting guide) TROUBLESHOOTING GUIDE 8.1 TROUBLESHOOTING The table below contains useful instructions to resolve any malfunctions or errors that may occur during installation or in case of a fault. Table 11 TROUBLESHOOTING Problems Recommended checks The radio transmitter does not control the Check whether the transmitter batteries are exhausted and replace them if necessary.
8.2 ANOMALY LOG press the button to shift the flashing LED to “L8”, that is, the “entry LED” for the “List of anomalies” param- The gearmotor allows for displaying any anomalies that oc- eter curred in the last 8 manoeuvres, for example, the interruption of press and hold the button.
8.4 SIGNALS ON THE CONTROL UNIT The control unit has a series of LEDs, each of which can emit special signals both during regular operation and when an FUSE anomaly occurs. A BlueBus LED B Close, Open, Sbs, Stop LEDs C “L1 ...
Page 24
Table 16 LEDS ON THE CONTROL UNIT BUTTONS LED 1 Description During normal operation, this indicates that “Automatic Closing” is disabled. During normal operation, this indicates that “Automatic Closing” is active. Function programming in progress. With the motor stationary, if it flashes individually it means that the encoder position is in the Low Overrun position (position below or equal to 5%).
FURTHER INFORMATION (Accessories) FURTHER DETAILS (Accessories) 9.1 MODIFYING THE STOP INPUT CONFIGURATION STOP is the input that causes immediate stoppage of the ma- noeuvre followed by its brief reversal. Devices with output fea- turing normally open “NO” and normally closed “NC” contacts, as well as devices with 8.2 kΩ...
9.3 CONNECTING AND INSTALLING THE BACK- Table 18 UP BATTERY OXI / OXIFM /OXIT / OXITFM IN MODE 2 EXTENDED Command Description The electrical connection of the battery to the con- “SbS” (Step-by-Step) command Step-by-Step trol unit must be made only after completing all the “Partial opening 1”...
insert the battery connection cable using a free cable in- insert the relative connector (C) on the control unit. 9.4 CONNECTING THE OVIEW PROGRAMMER The control unit has a BusT4 connector to which the “Oview” programmer can be connected, through the IBT4N interface. The programmer allows for fully and rapidly managing the in- stallation, maintenance and diagnosis of the entire automation.
9.5 CONNECTING THE SOLEMYO SOLAR ENERGY SYSTEM When the automation is powered by the “Solemyo” system, IT MUST NOT BE POWERED by the electricity grid at the same time. For information on the “Solemyo” system, consult the relevant instruction manual. To connect the “Solemyo”...
PRODUCT MAINTENANCE PRODUCT DISPOSAL The automation must be subjected to regular maintenance to PRODUCT MAINTENANCE PRODUCT DISPOSAL This product is an integral part of the operator and keep its safety level constant and guarantee long-lasting op- must therefore be disposed of with it. eration;...
TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS All technical specifications stated in this section refer to an ambient temperature of 20°C (± 5°C). Nice S.p.A. reserves the right to apply modifications to the product at any time when deemed necessary, without altering its functions and intended use.
“partly completed machinery” Note - The contents of this declaration correspond to declarations in the official document deposited at the registered offices of Nice S.p.a. and in particular to the last revision available before printing this manual. The text herein has been re-edited for editorial purposes. A copy of the original declaration can be requested from Nice S.p.a. (TV) I.
INSTRUCTIONS AND WARNINGS FOR THE USER Before using the automation for the first time, ask the installer to Safety devices out of order: the automation can also be used explain the origin of any residual risks and take a few minutes when one or more safety devices are defective or out of order.
Page 34
Unlocking and manual movement The gate can only be unlocked once the leaf has come to a standstill. The gearmotor is equipped with a mechanical unlocking device that can be used to open and close the door manually. These manual operations should only be performed in case of a power outage, malfunctions or during the installation phases.