Date:
/
/201
Circuit/System
Total current used (amps):
÷ Alternator rating (amps):
x 100% = Percent of alternator capacity used:
Notes:
[1] During taxi phase, utopilot circuit breaker is closed but autopilot is not engaged.
Figure 3-6 Example of Completed Tabulated Electrical Load Form
190-02246-10
Rev. 11
Tail Number:
N5272K
Circuit
Operating
Breaker
Time
Number
Pass/Fail:
Sheet 2 of 2
Phase(s) of flight during which circuit/system is used
Normal Operation
Taxiing
TO/Land
10 min
10 min
60.0
Ldg Lt ON
(b1)
45.7
(a)
44.7
Ldg Lt OFF
(b2)
70
86
%
Ldg Lt ON
(< 95%)
68
%
(< 80%)
64
%
Ldg Lt OFF
(< 80%)
PASS
PASS
GI 275 Part 23 AML STC Installation Manual
Emergency Operation
Cruise
Cruise
Land
60 min
(Calculated)
10 min
43.5
34
48.1
(c)
(d)
(e)
62
%
N/A
N/A
(< 80%)
PASS
Page 3-36