Transmitted data

6.1
Data from Modbus ® to the controller
The following function is provided for data transfer:
Modbus Function Code Designation
16 (10h)
Write multiple registers
The following data can be sent:
Word address
Word
Designation
address
hexadecimal
decimal
0000h
0000d
Actuate pump
(Only possible in
"Automatic"
mode!)
0001h
0001d
Actuate valves
(Only possible in
"Automatic"
mode!)
0002h
0002d
Pressure
specification for P0
0003h
0003d
Switch over the
operating mode
Note!
Remote control via the Modbus master is only possible, if this has been
enabled in the touch controller,  5.4 "Access codes",  21 (Settings >
Service > Configuration (211)).
Addressing
Word address / register
address [decimal]
Bit addresses
Bit 0 = pump / compressor 1 ON
Bit 1 = pump / compressor 1 OFF
Bit 2 = pump / compressor 2 ON
Bit 3 = pump / compressor 2 OFF
The pump is only controlled by
the controller process if neither
the bit for switching on nor the
bit for switching off a pump is
set.
Bit 0 = make-up valve OPEN
Bit 1 = make-up valve CLOSED
Bit 2 = overflow valve 1 OPEN
Servitec with 2x2W-KH: PV
open
Bit 3 = make-up overflow valve 1
CLOSED
Servitec with 2x2W-KH: PV
closed
Bit 4 = overflow valve 2 OPEN
Servimat: Spray tube
changeover
Servitec with 2x2W-KH: CD
closed
Bit 5 = make-up overflow valve 2
CLOSED
Servimat: Container
switchover
Servitec with 2x2-W-KH: CD
open
Bit 6 = valve MKH 2 OPEN
(Servimat only)
Bit 7 = valve MKH 2 CLOSED
(Servimat only)
The valve is only controlled by
the controller process if neither
the bit for switching on nor the
bit for switching off a valve is set.
Pressure value for "P0" in
1/10 bar
If the value "=" is transferred
here, then the actual setting in
the controller is not changed.
Bit 0 = operating mode  STOP
Bit 1 = operating mode 
AUTOMATIC
Anybus® - CompactCom / Modbus-RTU® — 08.11.2022 - Rev. B
6.2
Data from the controller to the Modbus ® (read operating data)
The following functions are provided for data retrieval
Modbus Function
Designation
Code
2
Read discrete inputs
3
Read multiple registers (from
address 100h  # = 1)
4
Read input registers (from address
000h  # = 0)
The following tables show the transmitted data for the various systems with a
Control Touch controller:
Variomat / Variomat Giga / Reflexomat
Servitec
Servimat
Peculiarities and options:
= For conductivity monitoring option only
*1
6.2.1

Transmitted data for Variomat / Variomat Giga / Reflexomat

Word
Word
address
address
Designation
hexadecimal
decimal
System pressure in
#10h
16d
1/100 bar
#11h
17d
Filling level in %
#12h
18d
Digital outputs
#13h
19d
Digital inputs
#14h
20d
Fault messages 1
Transmitted data
Addressing
Bit address
Word address
Word address
Bit addresses
---
---
120h: Compressor 2 or Pump 2 on
121h: Compressor 1 or Pump 1 on
122h: Overflow valve 2 open
123h: Overflow valve 1 open
124h: Make-up valve open
125h: Message: min. level
126h: Message Group alarm (1 = OK)
127h: Message: Make-up fault (only
for CT-MK200)
130h: Feedback Pump 1
131h: Feedback Pump 2
132h: Insufficient water switch
133h: Water meter
134h: Digital input DE5 (only for CT-
MK200)
135h: Digital input DE6 (only for CT-
MK200)
136h: Digital input DE7 (only for CT-
MK200)
140h: Expansion module fault
(Option)
141h: EEPROM defective
142h: Under voltage
143h: Below minimum pressure
144h: Low water 1
145h: Pump 1 faulty
146h: Compressor 1 faulty
147h: Pump 2 faulty
148h: Compressor 2 faulty
149h: Pressure measurement fault
14Ah: Level measurement fault
14Bh: longer than 4 hours in STOP
mode
14Eh: Balancing parameter incorrect
(main board)
14Fh: Communication faulty
(networking)
English — 25