Connecting the bus module
5.5
Read bit addresses
Based on the bit addresses, you can read off the respective parameters.
Example: Check whether the low water switch is on or off.
1.
In table 2, the low water switch 132h is listed under "Digital inputs".
•
Word address #19d or #13h (d = decimal; h = hexadecimal)
•
Index: 2
Table 2: The following data can be requested:
Designation
System pressure in 1/100 bar (not with Servitec
Levelcontrol)
Fill level in % (not with Servitec / here optional filling
pipe pressure in 1/100 bar)
Digital outputs
Digital inputs
Note!
Only decimal numbers can be entered in the ComTest Pro software. Hexadecimal numbers (h) must be converted to decimal numbers
"Convert number system",
2.
Open the ComTest Pro software and change the register in step 2 to 19 (= 19d, as the low water switch is stored under the word address 19d). Set the number of
registers to "1" (#Register), because only one parameter is to be read off.
3.
Press the "Start" button.
You will see a yellow-highlighted decimal number in the register history: 7d
22 — English
Word address /
register address
[decimal]
#16d
#17d
#18d
#19d
24.
Anybus® - CompactCom / Modbus-RTU® — 08.11.2022 - Rev. B
Word address / register
Bit addresses
address [hexadecimal]
#10h
---
#11h
---
#12h
120h (zeroth bit) - pump 2 on
121h (first bit) - pump 1 on
122h (second bit) - overflow valve 2 open
123h (third bit) - overflow valve 1 open
124h (fourth bit) - make-up valve open
125h (fifth bit) - message: min. level
126h (sixth bit) - message: Group fault
#13h
130h (zeroth bit) - pump 1 feedback
131h (first bit) - Pump 2 feedback
132h (second bit) - low water switch
133h (third bit) - water meter
(d),
5.5.1