Pin Assignment Of The 9-Pin D-Sub Connector; Access Codes - Reflex Anybus CompactCom Original Operating Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 17
Note!
If no module is listed in the menu, check the connections and whether
the bus module is correctly integrated.
6.
If a bus module has been detected, you can set the Modbus address
(module address), the baud rate and the data format in the controller.
Anybus® - CompactCom / Modbus-RTU® — 08.11.2022 - Rev. B
Note!
Each Modbus station must have a unique address for communicating.
Each Modbus address is encoded in a single byte.
Module address:
1 ... 247
Baud rates:
4800, 9600, 19200, 38400, 57600 baud
Data formats:
8/EVEN/1, 8/ODD/1, 8/NONE/2, 8/NONE/1
(data bits / parity / stop bits)
5.3

Pin assignment of the 9-pin D-sub connector

Pin
Designation
Function
1
GND
---
2
5 V
---
With RS-232: connect to pin 2
3
PMC
With RS-485: leave open!
4
-
---
5
B line
RS-485 signal B
6
-
---
7
Rx
RS-232 receive
8
Tx
RS-232 transmit
9
A line
RS-485 signal A
5.4

Access codes

Service menu access code:
Service:
Connecting the bus module
English — 21