Note! Reflex Winkelmann GmbH accepts no liability for any damage resulting from This symbol, in combination with the signal word 'Note', indicates failure to observe the information in this operating manual. In addition to the useful tips and recommendations for efficient handling of the product.
Factory set minimum operating pressure at site Set minimum operating pressure max. pressure saftey valve factory - aline Factory set actuating pressure of the safety valve at site Set actuating pressure of the safety valve Servimat M/L — 28.01.2021 4 — English...
Interfaces enable the use of additional Control Touch functions see chapter 6.4.3 The pressure relief valve means that the pump is set to a constant working "RS-485 interface" on page 13 . pressure. The working pressure depends on the respective facility system. Servimat M/L — 28.01.2021 English — 5...
The following optional equipment and accessories are available for this device: • Heat insulation for the primary tank a umso besser Servimat M/L connection diagram • Secondary tanks – Accessories are packed on the tank mounting •...
Wear protective gloves. (mm) (kg) (inches) (mm) (mm) • Please place appropriate warning signs in the vicinity of the device. 6 bar - 200 1060 6 bar - 300 1360 6 bar - 400 1345 Servimat M/L — 28.01.2021 English — 7...
For add-on components, proceed as follows: Execution Install the Reflex Exvoid (2) at the connection of the corresponding tank. For optimum reliability, we recommend braided sealing tape (PTFE) or pipe sealing cord (polyamide ww. PTFE) as a seal. ATTENTION Remove the protective cap from the degassing valve.
"Pump" connection set "Overflow collector" connection set Secondary tank connection • Align the primary tank. – The distance of the primary tank to the control unit must match the length of the connection set. Servimat M/L — 28.01.2021 English — 9...
6.3.4 "Tank installation" on page 9 . Comply with the following If required, install a bladder expansion vessel MAG ≥ 140 litres (Reflex N, for instructions: example).
Note! – Have the Reflex Customer Service carry out commissioning and If required, please contact the Reflex Customer Service for the protocol the annual maintenance. of the RS-485 interface, details of the connections and information about the accessories offered.
9.3 "Modifying the controller's ≥ p + 0.2 bar* (final start routine" on page 17 . pressure maintenance) Addition of 0.2 bar recommended, no addition in extreme cases Calculation example for "P " minimum operating pressure: Servimat M/L — 28.01.2021 14 — English...
The venting screw at the "PU" pump. After successful conclusion of the vacuum test, open the ball valve (2). If the controller displays the "Insufficient water" error message, acknowledge the message via button "OK". Servimat M/L — 28.01.2021 English — 15...
The change in the filling level and the tank pressure are indicated on the display. Note! Manual operation can not be performed if safety-relevant parameters are exceeded. – Switching is blocked if safety-relevant settings are exceeded. Servimat M/L — 28.01.2021 16 — English...
Touch the displayed crosses on the touch screen after each other. Always read the operating instructions prior to starting the system! Switch the device off and on again at the main switch. The touch screen is fully calibrated. Servimat M/L — 28.01.2021 English — 17...
– If null balancing is not successfully completed, you cannot commission the device. In this case, please contact Customer Service, see chapter 12.1 "Reflex Customer Service" on page 25 Set the time. – Use the "Left" and "Right" buttons to select the display value.
Brightness … % • Screen saver brightness … % This menu is protected with a password. It can be accessed only by the Reflex Customer Service. A partial summary of the settings stored in the Service menu is • Screen saver delay …min proved in the Chapter Default settings, see chapter 9.3.3 "Default settings"...
Press "Customer >". – The controller opens the Customer menu. Press "Degassing >". – The controller switches to the selected area. – Use the scroll bar to navigate through the list. Servimat M/L — 28.01.2021 20 — English...
RS-485 interface or via two floating message contacts. The controller displays the messages with a help text. Message causes can be eliminated by the operator or a specialist workshop. If this is not possible, contact the Reflex Customer Service. Note! When the cause for the message is eliminated, you must acknowledge –...
Page 22
Replace battery unit (CPU). • Bus module activated but not • Connect bus module. Bus module present. • Check connection cable. • Connecting cable defective. • Replace bus module. • Bus module defective. Servimat M/L — 28.01.2021 22 — English...
Before testing pressurised parts, they must first be depressurised • Ensure proper installation, removal or maintenance work. (see Removal). Arrange for Reflex Customer Service to perform the inspection. • Ensure that the system is de-pressurised before performing installation, To contact Reflex Customer Service, see chapter 12.1 "Reflex Customer Service"...
10. Switch to Automatic mode. 10.5 Maintenance certificate 10.4 Checking switching points All maintenance tasks have been completed according to the Reflex Installation, Operating and Maintenance Manual. Prerequisite for checking the switching points are the following correct settings: • Minimum operating pressure P , see chapter 7.2 "Determining the P...
Ensure that installation work for the electric connection of the device is 12.2 Conformity and standards carried out by an electrician, and in compliance with electrical engineering regulations. Device conformity declarations are available on the Reflex homepage. www.reflex-winkelmann.com/konformitaetserklaerungen CAUTION Alternatively, scan the QR code: Risk of burns Escaping hot medium can cause burns.