Servimat M/L
Pressure maintenance with degassing
GB
Operating manual
Original operating manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Servimat M and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Reflex Servimat M

  • Page 1 09.04.2019 Servimat M/L Pressure maintenance with degassing Operating manual Original operating manual...
  • Page 2: Table Of Contents

    Disassembly ................25 Electrical connection ..............10 Annex ..................25 6.4.1 Terminal plan, connection component ....... 11 12.1 Reflex Customer Service ............25 6.4.2 Terminal plan, operating unit ........12 12.2 Conformity and standards ............25 6.4.3 RS-485 interface .............. 13 12.3...
  • Page 3: Notes On The Operating Manual

     Note! Reflex Winkelmann GmbH accepts no liability for any damage resulting from This symbol, in combination with the signal word 'Note', indicates failure to observe the information in this operating manual. In addition to the useful tips and recommendations for efficient handling of the product.
  • Page 4: Inadmissible Operating Conditions

    Factory set minimum operating pressure at site Set minimum operating pressure max. pressure saftey valve factory - aline Factory set actuating pressure of the safety valve at site Set actuating pressure of the safety valve Servimat M/L — 28.01.2021 4 — English...
  • Page 5: Type Code

    Interfaces enable the use of additional Control Touch functions see chapter 6.4.3 The pressure relief valve means that the pump is set to a constant working "RS-485 interface" on page 13 . pressure. The working pressure depends on the respective facility system. Servimat M/L — 28.01.2021 English — 5...
  • Page 6: Scope Of Delivery

    The following optional equipment and accessories are available for this device: • Heat insulation for the primary tank a umso besser Servimat M/L connection diagram • Secondary tanks – Accessories are packed on the tank mounting •...
  • Page 7: Dimensions And Connections

    Wear protective gloves. (mm) (kg) (inches) (mm) (mm) • Please place appropriate warning signs in the vicinity of the device. 6 bar - 200 1060 6 bar - 300 1360 6 bar - 400 1345 Servimat M/L — 28.01.2021 English — 7...
  • Page 8: Incoming Inspection

    For add-on components, proceed as follows: Execution Install the Reflex Exvoid (2) at the connection of the corresponding tank. For optimum reliability, we recommend braided sealing tape (PTFE) or pipe sealing cord (polyamide ww. PTFE) as a seal. ATTENTION Remove the protective cap from the degassing valve.
  • Page 9: Tank Installation

    "Pump" connection set "Overflow collector" connection set Secondary tank connection • Align the primary tank. – The distance of the primary tank to the control unit must match the length of the connection set. Servimat M/L — 28.01.2021 English — 9...
  • Page 10: Fitting The Thermal Insulation

    6.3.4 "Tank installation" on page 9 . Comply with the following If required, install a bladder expansion vessel MAG ≥ 140 litres (Reflex N, for instructions: example).
  • Page 11: Terminal Plan, Connection Component

    X0/1 “Safe Control” motorized ball Factory- X0/2 valve for make-up (MKH1) WV provided X0/3 Supply 400 V, maximal 20 A User supplied X0/4 Motorized ball valve to the tank Factory- X0/5 (MKH2) provided Servimat M/L — 28.01.2021 English — 11...
  • Page 12: Terminal Plan, Operating Unit

    GNDA supplied (feedback) Standard 4 – 20 mA Level GNDA +24 V (supply) 0 – 10 V Pressure relief valve (control Factory- (correcting ball valve RKH1) provided variable) 0 – 10 V (feedback) Servimat M/L — 28.01.2021 12 — English...
  • Page 13: Rs-485 Interface

     Note! – Have the Reflex Customer Service carry out commissioning and If required, please contact the Reflex Customer Service for the protocol the annual maintenance. of the RS-485 interface, details of the connections and information about the accessories offered.
  • Page 14: Filling The Device With Water And Venting

    9.3 "Modifying the controller's ≥ p + 0.2 bar* (final start routine" on page 17 . pressure maintenance) Addition of 0.2 bar recommended, no addition in extreme cases Calculation example for "P " minimum operating pressure: Servimat M/L — 28.01.2021 14 — English...
  • Page 15: Vacuum Test

    The venting screw at the "PU" pump. After successful conclusion of the vacuum test, open the ball valve (2). If the controller displays the "Insufficient water" error message, acknowledge the message via button "OK". Servimat M/L — 28.01.2021 English — 15...
  • Page 16: Operation

    The change in the filling level and the tank pressure are indicated on the display.  Note! Manual operation can not be performed if safety-relevant parameters are exceeded. – Switching is blocked if safety-relevant settings are exceeded. Servimat M/L — 28.01.2021 16 — English...
  • Page 17: Controller

    Touch the displayed crosses on the touch screen after each other. Always read the operating instructions prior to starting the system! Switch the device off and on again at the main switch. The touch screen is fully calibrated. Servimat M/L — 28.01.2021 English — 17...
  • Page 18: Customer Menu

    – If null balancing is not successfully completed, you cannot commission the device. In this case, please contact Customer Service, see chapter 12.1 "Reflex Customer Service" on page 25 Set the time. – Use the "Left" and "Right" buttons to select the display value.
  • Page 19: Service Menu

    Brightness … % • Screen saver brightness … % This menu is protected with a password. It can be accessed only by the Reflex Customer Service. A partial summary of the settings stored in the Service menu is • Screen saver delay …min proved in the Chapter Default settings, see chapter 9.3.3 "Default settings"...
  • Page 20: Degassing Programmes - Overview

    Press "Customer >". – The controller opens the Customer menu. Press "Degassing >". – The controller switches to the selected area. – Use the scroll bar to navigate through the list. Servimat M/L — 28.01.2021 20 — English...
  • Page 21: Messages

    RS-485 interface or via two floating message contacts. The controller displays the messages with a help text. Message causes can be eliminated by the operator or a specialist workshop. If this is not possible, contact the Reflex Customer Service.  Note! When the cause for the message is eliminated, you must acknowledge –...
  • Page 22 Replace battery unit (CPU). • Bus module activated but not • Connect bus module. Bus module present. • Check connection cable. • Connecting cable defective. • Replace bus module. • Bus module defective. Servimat M/L — 28.01.2021 22 — English...
  • Page 23: Maintenance

    Before testing pressurised parts, they must first be depressurised • Ensure proper installation, removal or maintenance work. (see Removal). Arrange for Reflex Customer Service to perform the inspection. • Ensure that the system is de-pressurised before performing installation, To contact Reflex Customer Service, see chapter 12.1 "Reflex Customer Service"...
  • Page 24: Cleaning The Tanks

    10. Switch to Automatic mode. 10.5 Maintenance certificate 10.4 Checking switching points All maintenance tasks have been completed according to the Reflex Installation, Operating and Maintenance Manual. Prerequisite for checking the switching points are the following correct settings: • Minimum operating pressure P , see chapter 7.2 "Determining the P...
  • Page 25: Inspection

    Ensure that installation work for the electric connection of the device is 12.2 Conformity and standards carried out by an electrician, and in compliance with electrical engineering regulations. Device conformity declarations are available on the Reflex homepage. www.reflex-winkelmann.com/konformitaetserklaerungen CAUTION Alternatively, scan the QR code: Risk of burns Escaping hot medium can cause burns.
  • Page 26 Reflex Winkelmann GmbH Gersteinstraße 19 59227 Ahlen, Germany +49 (0)2382 7069-0 +49 (0)2382 7069-9546 www.reflex-winkelmann.com...