Floor Clearance; Floor Strength And Inclination; Overhead Clearance; Power And Grounding - Quantum P1000 Series User Manual

Automated tape library
Hide thumbs Also See for P1000 Series:
Table of Contents

Advertisement

Figure 10 Floor Space
Requirements,
Rack-mount Library
17.5 in.
(45 cm)

Floor Clearance

Floor Strength and
Inclination

Overhead Clearance

Power and Grounding

Figure 10 shows the floor space requirements for the rack-mount
P1000.
24 in. (61 cm)
Back
The stand-alone P1000 has a floor clearance of 0.75 in. (1.9 cm). Place
2
the library on a level, uncarpeted floor free of defects.
The floor at the installation site must be rated at 250 lb/ft
2
(1221 kg/m
). This is sufficient to support a fully loaded P1000 on the
2
floor or in a rack.
The floor at the installation site must be level to within 0.25 in (6.4 mm)
over a 6 ft by 6 ft (1.8 m by 1.8 m) area.
To remove the P1000 enclosure, there must be a minimum clearance of
2
24 in. (61 cm) above the library. When combined with the height of the
library (21 in./53 cm), this is a total of 45 in. (114.5 cm) from the floor
(stand-alone library) or bottom of the slide (rack-mount library).
The library auto-ranging power supply accepts single-phase, 90 VAC
2
to 264 VAC input power at 47 Hz to 63 Hz.
ATL P1000 Series User's Guide
19-inch rack
30 in. (76.2 cm)
Chapter 2 Installing the P1000 Library
Site Requirements
24 in.
(61 cm)
each side
Library
(extended
(61 cm)
from rack)
2
Front
24 in.
15