Quantum ActiveScale P100E3 Site Preparation And Requirements Manual

With activescale os 6.1.0 software
Hide thumbs Also See for ActiveScale P100E3:

Advertisement

Quick Links

ActiveScale
with ActiveScale OS 6.1.0 software
P100E3 Site Requirements Guide
6-68926-04, Rev. A

Advertisement

Table of Contents
loading

Summary of Contents for Quantum ActiveScale P100E3

  • Page 1 ActiveScale with ActiveScale OS 6.1.0 software P100E3 Site Requirements Guide 6-68926-04, Rev. A...
  • Page 2 Quantum ActiveScale™ P100E3 Site Requirements Guide, 6-68837-04, March 2022, Product of USA. Quantum Corporation provides this publication “as is” without warranty of any kind, either express or implied, including but not limited to the implied warranties of merchantability or fitness for a particular purpose. Quantum Corporation may revise this publication from time to time without notice.
  • Page 3: Table Of Contents

    2 ActiveScale P100E3 site requirements ........
  • Page 4 ActiveScale™ P100E3 Site Requirements Guide...
  • Page 5: List Of Tables

    ActiveScale™ P100E3 Site Requirements Guide List of tables List of tables Table 1-1. System specification summary ........10 Table 2-1.
  • Page 6 ActiveScale™ P100E3 Site Requirements Guide List of tables...
  • Page 7: List Of Figures

    Figure 1-1. ActiveScale P100E3 system layout ....... . . 9...
  • Page 8 ActiveScale™ P100E3 Site Requirements Guide List of figures...
  • Page 9: Document Summary

    ActiveScale™ P100E3 Site Requirements Guide 1 Document summary This chapter defines the scope of this document and provides a brief overview of the ActiveScale P100E3 system site requirements. Topics: • Scope on page 9 • Product overview on page 9 •...
  • Page 10: System Specification Summary

    ActiveScale™ P100E3 Site Requirements Guide 1.3 System specification summary The following table is a summary of specifications relevant to the ActiveScale P100E3 system. Table 1-1. System specification summary Condition (fully configured) Non-operating Operating Altitude -984 ft to 39,371 ft -984 ft to 10,000 ft...
  • Page 11: Activescale P100E3 Site Requirements

    2.3 Rack requirements The ActiveScale P100E3 is installed into a customer-supplied rack. Use the guidelines in this section to choose an appropriate rack mounting solution. Important: The absolute minimum depth requirement for the ActiveScale P100E3 is 42.12 in (1070 mm).
  • Page 12: Delivery Route Inspection

    • Security—Make sure that all site security requirements adhered to and that all personnel are made aware of the parameters under which they must work. 2.5 Build space requirements The ActiveScale P100E3 is delivered on a pallet and installed on-site. This section describes the space required for unpacking and installation. Table 2-1. Footprint of packaging...
  • Page 13: Servicing Space Requirements

    Important: Mounting a PDU or other equipment vertically in the rack can hinder the ability to service components. To properly install and service system components, the ActiveScale P100E3 system requires space at the front and rear of the system. Table 2-3. Space requirement specifications...
  • Page 14: Pdu Requirements

    ActiveScale™ P100E3 Site Requirements Guide 2.7 PDU requirements The ActiveScale P100E3 does not come with its own power distribution unit (PDU). This section provides information about selecting a PDU that will effectively and safely support system power consumption. Parameter Power conector type All connectors on each component are C14.
  • Page 15 ActiveScale™ P100E3 Site Requirements Guide optimized fiber). These cables must comply with the Ethernet 10GBASE-SR standard. Ensure that you do not exceed the specified maximum 10GBASE-SR cable length for the cable type chosen. For example, do not exceed a length of 400 m if you are using 10G OM4 multi-mode cables.
  • Page 16 ActiveScale™ P100E3 Site Requirements Guide...
  • Page 17: Contacting Support

    ActiveScale™ P100E3 Site Requirements Guide Contacting Support Contacting Support For further assistance, contact the Quantum Corporation Support Center. Region Support Contact North America 1-800-284-5101 (toll free) +1-720-249-5700 EMEA +1-800-7826-8888 (toll free) +49 6131 324 185 Asia Pacific +800-7826-8887 (toll free)