HPE ProLiant ML350 Gen11 User Manual page 176

Hide thumbs Also See for ProLiant ML350 Gen11:

Advertisement

Subtopics
Subtopics
Environmental specifications
Environmental specifications
Limited operating inlet ambient temperature requirements
Limited operating inlet ambient temperature requirements
Mechanical specifications
Mechanical specifications
Power supply specifications
Power supply specifications
Environmental specifications
Environmental specifications
Specifications
Specifications
Temperature range*
Temperature range*
Operating
Nonoperating
Relative humidity (noncondensing)
Relative humidity (noncondensing)
Operating
Nonoperating
Altitude
Altitude
Operating
Nonoperating
Standard operating support
Standard operating support
10° to 35°C (50° to 95°F) at sea level with an altitude derating of 1.0°C per every 305 m (1.8°F per every 1,000 ft) above sea level to a
maximum of 3,050 m (10,000 ft), no direct sustained sunlight. Maximum rate of change is 20°C/hr​ (36°F/hr). The upper limit and rate of
change may be limited by the type and number of options installed.
System performance during standard operating support might be reduced in the following conditions:
A fan failure occurs.
The server operates above 30°C (86°F).
Extended ambient operating support
Extended ambient operating support
For approved hardware configurations, the supported system inlet range is extended to be:
5° to 10°C (41° to 50°F) and 35° to 40°C (95° to 104°F) at sea level with an altitude derating of 1.0°C per every 175 m (1.8°F per
every 574 ft) above 900 m (2,953 ft) to a maximum of 3050 m (10,000 ft).
40°C to 45°C (104°F to 113°F) at sea level with an altitude derating of 1.0°C per every 125 m (1.8°F per every 410 ft) above 900 m
(2953 ft) to a maximum of 3,050 m (10,000 ft).
The approved hardware configurations for this system are listed in the Extended Ambient Temperature Guidelines for Gen11 HPE
ProLiant servers:
https://www.hpe.com/support/ASHRAEGen11
https://www.hpe.com/support/ASHRAEGen11
Limited operating inlet ambient temperature requirements
Limited operating inlet ambient temperature requirements
Value
Value
10°C to 35°C (50°F to 95°F)
-30°C to 60°C (-22°F to 140°F)
8% to 90%
28°C (82.4°F) maximum wet bulb temperature, noncondensing
5% to 95%
38.7°C (101.7°F) maximum wet bulb temperature, noncondensing
3050 m (10,000 ft)
This value may be limited by the type and number of options installed. Maximum
allowable altitude change rate is 457 m/min (1,500 ft/min).
9144 m (30,000 ft)
Maximum allowable altitude change rate is 457 m/min (1,500 ft/min).
HPE ProLiant ML350 Gen11 Server User Guide
176