6: Drive Enclosure Operation
Turning the Power On After an Overtemp Shutdown
88
Overtemp Indicator
Figure 6-2
Overtemp, Power, and Fault Indicators
Use this procedure to restart the drive enclosure after a unexpected shutdown due to an
overtemp condition.
1.
Turn off both power switches (Figure 6-1).
2. Do whatever is necessary to cool the drive enclosure (replace the fans, use external
fans to cool the room, and so on).
Warning:
Risk of severe electrical shock. Never turn on the power to any
equipment when there is evidence of fire, water, or structural damage. If there is
evidence of damage, call the factory or appropriate service organization for
assistance. Depending on the current service agreements, you may need to send
the unit back to the factory for repair/replacement.
3. Check all components and cables for visible damage. Do not start the drive
enclosure if you find evidence of damage.
Note: To speed drive spin-up, it is recommended that you start the drive enclosures
before or at the same time as the controller enclosure.
Power Indicator
Fault Indicator
55008-c
007-4304-003