Operation
}
The LED lights for 4 s continuously after "Startup" operating status has been run. During
this time it's possible to change to "Boot Menu" operating status.
}
Press the reset pushbutton while the LED is lit continuously.
}
The controller changes to "Boot Menu".
Hardware reset (cold start)
A hardware reset can be triggered in "RUN" or "STOP" operating status. The controller
changes to "Startup" operating status.
Follow the instructions below:
}
The controller is in "STOP" or "RUN" operating status.
}
Hold the reset pushbutton down for at least 4 s.
}
The controller changes to "Startup".
Changing between the operating states "RUN" and "STOP"
You can change between the operating states "RUN" and "STOP".
}
Briefly press the reset pushbutton to change from "RUN" to "STOP" or from "STOP" to
"RUN".
9.4

Messages

The motion controller provides many options for diagnostics, fault detection and communic-
ation with other controllers.
Diagnostics can be performed via
}
The LEDs on the front of the device.
}
The error stack.
}
PVIS expanded diagnostics.
}
Display commands.
}
Recording of process data.
LEDs
LEDs on the front of the device provide information on the operating status (see section on
"Display elements" in this chapter).
Error stack
The error stack contains the last 100 error messages. It can be read in the operating status
"RUN" and "STOP".
}
Select the LE1 command in the terminal program.
PVIS
Errors, messages and the corresponding remedies are displayed in the expanded dia-
gnostics system PVIS.