We do assure you that all persons are regarded without discrim- ination and on an equal basis. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
Dimensions ..........................Installing the head module......................Interfaces ..........................Interface configuration ......................6.1.1 PROFIBUS DP ......................... 6.1.2 Ethernet ............................ Wiring ............................General wiring guidelines ......................Terminal configuration ......................Connecting the module......................Operating Manual PSSu H m F DP ETH SD 1002323-EN-06...
Page 4
X3: LNK, X3: TRF ........................Technical details ........................Safety characteristic data ......................Order reference ........................10.1 Product ............................. 10.2 Accessories ..........................EC declaration of conformity ....................UKCA-Declaration of Conformity ..................Operating Manual PSSu H m F DP ETH SD 1002323-EN-06...
Introduction Introduction Validity of the documentation This documentation is valid for the product type PSSu H m F DP ETH SD. It is valid until new documentation is published. Please also refer to the following documents: PSS4000 System Description PSSuniversal Installation Manual This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
The request for the source code must be received 3 years at the latest after the receipt of the relevant GPL or LPGL. Irrespective of this period we will send you a complete, ma- chine-readable copy of the source code as long as Pilz offers spares or technical support for this device.
– Module supply is buffered for 20 ms if the supply voltage is interrupted – Plug-in connection terminals (either spring-loaded terminal or screw terminal) Status LEDs Supports FS and ST modules Operating Manual PSSu H m F DP ETH SD 1002323-EN-06...
The labelling strip contains the following information: Order number 312060 Serial number 100017 Hardware version HW 001 2D code: Product information MAC address 0002 4840 3152 2D code: MAC address Operating Manual PSSu H m F DP ETH SD 1002323-EN-06...
Any use of the module that is not in accordance with the technical details. INFORMATION The module is supported by PAS4000 from Version 1.5.0. We recommend that you always use the latest version (download from www.pilz.de). Safety regulations 3.2.1 Use of qualified personnel The products may only be assembled, installed, programmed, commissioned, operated, maintained and decommissioned by persons who are competent to do so.
In safety-related applications, please comply with the mission time T in the safety-related characteristic data. When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PSSu H m F DP ETH SD | 10 1002323-EN-06...
When the supply voltage is fed in separately, the module supply and periphery supply are galvanically isolated. If galvanic isolation is not required, a common power supply may be used for the periphery supply and module supply. Operating Manual PSSu H m F DP ETH SD | 11 1002323-EN-06...
However, the "24 V" LED will light and a message will be entered in the dia- gnostic list. Please refer to the derating diagram. Derating diagram for periphery supply: Temperature T dependent on load current I T (°C) I (A) Operating Manual PSSu H m F DP ETH SD | 12 1002323-EN-06...
Files may be damaged if the card is removed from the device or the power to the device is switched off as the SD card is being written. Remove the SD card only in recovery mode or in switched-off state. Operating Manual PSSu H m F DP ETH SD | 13 1002323-EN-06...
. If station address 126 is set via the DIP switch, the address can be assigned via the Master. The Set Slave Address com- mand (SSA) must be run for this purpose. Operating Manual PSSu H m F DP ETH SD | 14 1002323-EN-06...
Page 15
The station address should only be set when the module is switched off (no voltage applied). The settings are only transferred when booting. Any changes made to the settings during operation will not be transferred. Operating Manual PSSu H m F DP ETH SD | 15 1002323-EN-06...
The Ethernet interface is configured in PAS4000 (see description in chapter "Network" in PAS4000's online help). 4.8.2 RJ45 connection cable RJ45 connector 8-pin 10BaseT cable or 100BaseTX cable max. 100 m Operating Manual PSSu H m F DP ETH SD | 16 1002323-EN-06...
Dimensions 130 mm 83,3 mm (3.28'') (5.19'') 50 mm 79,1 mm (1.97'') (3.11'') 32,1 mm (1.26'') Operating Manual PSSu H m F DP ETH SD | 17 1002323-EN-06...
Push the head module back as far as it will go [2]. Make sure that the locking mechanisms [3] are pushed downwards, connecting the mod- ule firmly to the mounting rail. Schematic representation: Operating Manual PSSu H m F DP ETH SD | 18 1002323-EN-06...
Do not use the signals VP (+5 V ext.) and DGND (GND ext.) to supply voltage to external devices! They are exclusively used to supply the PROFIBUS DP bus terminating resistors. Operating Manual PSSu H m F DP ETH SD | 19 1002323-EN-06...
(e.g. EN 60204-1, NFPA 79:17-7, NEC: Art- icle 250). Details of the minimum range for conductor cross sections on connection terminals can be found in the section entitled "Technical Details". Use copper wiring. Operating Manual PSSu H m F DP ETH SD | 21 1002323-EN-06...
Periphery supply Terminal configuration 4-pin female con- 24V: +24 V infeed for peri- nector phery supply 24V 24V 0V 0V 0 V infeed for periphery supply Functional earth Operating Manual PSSu H m F DP ETH SD | 22 1002323-EN-06...
Common power supply for module supply and periphery supply: Infeed for Module Supply 10 A Infeed for Periphery Supply Connect to the 0 V supply and earth at exactly this point Operating Manual PSSu H m F DP ETH SD | 23 1002323-EN-06...
OPC Server and PSS 4000 Diag Control. Display elements The head module contains a number of status LEDs, which provide information on the status of various system sections. LEDs on the PSSu H m F DP ETH SD: MBUS SD CARD FS RUN...
(e.g. a module has been removed during operation, actual/ registered hardware does not match) Operating state "FS module bus in a STOP condition with error: Major FS error" Operating Manual PSSu H m F DP ETH SD | 25 1002323-EN-06...
SD card can be removed. Green-red Naming data and device project on the PSSu system and SD card do not match Orange Device identification activated by user Operating Manual PSSu H m F DP ETH SD | 26 1002323-EN-06...
- Task in TERMINATED condition or - Task in STOP condition At least one FS resource task is not running. The project is unlicensed. Only one task is present on the FS resource. Operating Manual PSSu H m F DP ETH SD | 27 1002323-EN-06...
Orange A message of at least "Warning" severity is present for the device (see diagnostic list). Red - green Start of "deliberate operator action" (function of reset button) Operating Manual PSSu H m F DP ETH SD | 28 1002323-EN-06...
On the FS resource, forcing is inactive and there is no on- line change active yellow On the FS resource, forcing is active and/or there is at least one online change active Operating Manual PSSu H m F DP ETH SD | 29 1002323-EN-06...
The "24 V" LED shows the status of the periphery supply. Colour Status Meaning - - - No supply voltage for periphery supply or supply voltage is faulty Green Periphery supply is available on the module bus Operating Manual PSSu H m F DP ETH SD | 30 1002323-EN-06...
Ethernet/SafetyNET p interface are displayed via the LEDs. X3: LNK Colour State No network connection Green Network connection is error-free X3: TRF Colour State No data traffic yellow Data traffic is error-free Operating Manual PSSu H m F DP ETH SD | 31 1002323-EN-06...
Max. continuous current that the external power supply must provide 10 A Potential isolation between module supply and peri- phery supply 3050 V Potential isolation between module supply and PROFIBUS-DP 700 V Operating Manual PSSu H m F DP ETH SD | 32 1002323-EN-06...
Page 33
MBit/s, 45,45 kBit/s, 500 kBit/s, 6 MBit/s, 9,6 kBit/ s, 93,75 kBit/s Transmission rate selectable via Automatic Connection 9-pin D-Sub female connector DPV0 Operating modes AutoBaud, Freeze Mode, Set Slave Address, Sync Mode Certification Operating Manual PSSu H m F DP ETH SD | 33 1002323-EN-06...
Page 34
In accordance with the standard EN 60068-2-27 Number of shocks 1000 Acceleration Duration 16 ms Airgap creepage In accordance with the standard EN 60664-1 Overvoltage category Pollution degree Operating Manual PSSu H m F DP ETH SD | 34 1002323-EN-06...
Page 35
Stripping length with spring-loaded terminals 9 mm Dimensions Height 125,6 mm Width 130 mm Depth 83,7 mm Weight 375 g Where standards are undated, the 2009-07 latest editions shall apply. Operating Manual PSSu H m F DP ETH SD | 35 1002323-EN-06...
IEC 61511 IEC 61511 EN ISO mode 13849-1: 13849-1: 13849-1: SIL CL [1/h] 2015 2015 2015 Category [year] – PL e Cat. 4 SIL CL 3 4,14E-09 SIL 3 3,51E-05 Operating Manual PSSu H m F DP ETH SD | 36 1002323-EN-06...
10.2 Accessories Terminals Product type Features Order no. PSSu A Con 1/4 S 2 x screw terminals 313110 PSSu A Con 2/8 C 2 x spring-loaded terminals 313111 Operating Manual PSSu H m F DP ETH SD | 37 1002323-EN-06...
European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/downloads. Authorised representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ostfildern, Germany Operating Manual PSSu H m F DP ETH SD...
The complete UKCA Declaration of Conformity is available on the Internet at www.pilz.com/ support/downloads. Representative: Pilz Automation Technology, Pilz House, Little Colliers Field, Corby, Northamptonshire, NN18 8TJ United Kingdom, eMail: mail@pilz.co.uk Operating Manual PSSu H m F DP ETH SD | 39 1002323-EN-06...
Page 40
We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters. Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com...
Need help?
Do you have a question about the PSSu H m F DP ETH SD and is the answer not in the manual?
Questions and answers