Wiring

7
Wiring
7.1

Wiring guidelines

Please note:
}
Cable cross sections for field connection terminals in mm
– Digital inputs/outputs, supply voltage: 0.5 (AWG20) ... 1.0 (AWG18), AEH without
Inputs
}
Appropriate wiring must be used to exclude short circuits between the inputs or to a sup-
ply line.
}
Cables must be shielded if the signals are used as reference inputs. Other signal lines do
not need to be shielded.
Outputs
}
If short circuits occur between the cable from the output to the load and a supply line, it
will no longer be possible to switch off the load.
Possible remedy: Use separate multicore cable for supply voltages.
}
Use appropriate wiring to exclude short circuits between the outputs.
}
The actuators may be connected using unshielded cables.
}
The outputs do not need suppression for inductive loads.
Cable material
}
Use copper wiring.