PNOZ m ES Profibus Configurable control systems PNOZmulti 2 Operating Manual 1002698-EN-05...
Page 2
Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
6.1.2 Connecting the supply voltage 6.1.3 PROFIBUS DP interface Preparing for operation 6.2.1 Setting the station address 6.2.2 Download modified project to the control system PNOZmulti 6.2.3 Connection example Section 7 Operation Messages Operating Manual PNOZ m ES Profibus 1002698-EN-05...
Page 4
Contents Section 8 Technical details Section 9 Order reference Product Accessories Operating Manual PNOZ m ES Profibus 1002698-EN-05...
Introduction Introduction Validity of documentation This documentation is valid for the product PNOZ m ES Profibus. It is valid until new docu- mentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
Page 6
Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PNOZ m ES Profibus 1002698-EN-05...
In the PNOZmulti Configurator, 128 virtual outputs of the PNOZmulti 2 control system can be defined for communication with the fieldbus PROFIBUS-DP . Max. 1 PNOZ m ES Profibus can be connected to the base unit Plug-in connection terminals: either spring-loaded terminal or screw terminal available as an accessory (see order reference) Please refer to the document "PNOZmulti System Expansion"...
- x10 = Tens digit for the station address - x1 = Units digit for the station address X1: PROFIBUS-DP interface (female 9-pin D-Sub connector) X4: 0 V, 24 V: Supply connections Functional earth Operating Manual PNOZ m ES Profibus 1002698-EN-05...
Safety Safety Intended use The expansion module PNOZ m ES Profibus is used for communication between the con- figurable control system PNOZmulti 2 and PROFIBUS-DP. PROFIBUS-DP is designed for fast data exchange at field level. The expansion module PNOZ m ES Profibus is a passive subscriber (Slave) of PROFIBUS-DP (DPV0). The basic functions of communication with PROFIBUS-DP conform to EN 50170.
Do not open the housing or make any unauthorised modifications. Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors). Operating Manual PNOZ m ES Profibus 1002698-EN-05...
ES Profibus are connected via a jumper. The station address is set via rotary switches. After the supply voltage is switched on or the control system PNOZmulti 2 is reset, the expansion module PNOZ m ES Profibus is con- figured and started automatically.
Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. Dimensions in mm 22,5 101,4 (4,11“) (0,88“) Operating Manual PNOZ m ES Profibus 1002698-EN-05...
Please refer to the document "PNOZmulti System Expansion" for details of the number of modules that can be connected to the base unit and the module types. Operating Manual PNOZ m ES Profibus 1002698-EN-05...
Connect the supply voltage to the fieldbus module: 24 V terminal: + 24 VDC 0 V terminal: 0 V Protect the supply voltage as follows: – Circuit breaker, characteristic C - 6 A – Blow-out fuse, slow, 6A Operating Manual PNOZ m ES Profibus 1002698-EN-05...
9: n.c. n.c. = not connected Please note the following when connecting to PROFIBUS-DP: Only use metal plugs or metallised plastic plugs Twisted pair, screened cable must be used to connect the interfaces Operating Manual PNOZ m ES Profibus 1002698-EN-05...
6.2.1 Setting the station address The station address of the expansion module PNOZ m ES Profibus is set between 0 ... 99 (decimal) via two rotary switches x1 and x10. On the upper rotary switch x10, use a small screwdriver to set the tens digit for the ad- dress (“3”...
Commissioning 6.2.3 Connection example PROFIBUS-DP PROFIBUS-DP PROFIBUS-DP Slave n Slave 1 Slave 3 PROFIBUS-DP Master PNOZ m ES PROFIBUS PROFIBUS-DP Slave 2 Operating Manual PNOZ m ES Profibus 1002698-EN-05...
If the expansion module PNOZ m ES Profibus does not receive a configuration from the base unit for a period of 30 s, the expansion module PNOZ m ES Profibus connects to PROFIBUS-DP and the "ONLINE" status is displayed on the PROFIBUS-DP. The error message "No Connection with Base Module"...
Page 20
Ensure that the right GSD file has been used. 2 Hz Configuration error, length/content of the configuration data during initialisation of the PNOZ m ES Profibus does not match the configuration Remedy: Ensure that the right GSD file has been used.
Page 21
Condensation during operation Not permitted EN 61131-2 Vibration In accordance with the standard EN 60068-2-6 Frequency 10,0 - 150,0 Hz Acceleration Shock stress In accordance with the standard EN 60068-2-27 Acceleration Duration 11 ms Operating Manual PNOZ m ES Profibus 1002698-EN-05...
Page 22
Spring-loaded terminals: Terminal points per connec- tion Stripping length with spring-loaded terminals 9 mm Dimensions Height 101,4 mm Width 22,5 mm Depth 115,0 mm Weight 95 g Where standards are undated, the 2012-10 latest editions shall apply. Operating Manual PNOZ m ES Profibus 1002698-EN-05...
Page 24
Front cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95446300 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland Mexico +43 1 7986263-0 +41 62 88979-30...