Diagnostics and Troubleshooting
User Manual
4.10 Clearing a Fault Condition
Typically, if the OK LED on the front of the module turns RED for more than ten
seconds, a hardware problem has been detected in the module or the program
has exited.
To clear the condition, follow these steps:
Turn off power to the rack.
1
2
Remove the card from the rack.
3
Verify that all jumpers are set correctly.
If the module requires a Compact Flash card, verify that the card is installed
4
correctly.
5
Re-insert the card in the rack and turn the power back on.
Verify correct configuration data is being transferred to the module from the
6
ControlLogix controller.
If the module's OK LED does not turn GREEN, verify that the module is inserted
completely into the rack. If this does not cure the problem, contact ProSoft
Technology Technical Support.
Page 106 of 175
MVI56E-MNETR ♦ ControlLogix Platform
Modbus TCP/IP Interface Module with Reduced Data Block
ProSoft Technology, Inc.
June 14, 2011