6.2 SHUTDOWN ALARM

When controller detects shutdown alarm, it will send signal to open breaker and shuts down generator.
No.
Type
1
Emergency Stop
2
Over Speed
3
Under Speed
4
Loss of Speed Signal
5
Gen Over Frequency
6
Gen Under Frequency
7
Gen Over Voltage
8
Genset Under Voltage
9
Fail To Stop
10
Gen Over Current
HGM9510 Genset Parallel Controller User Manual
will initiate a warning alarm.
When the controller detects the imbalance current has exceeded the
pre-set value and the action selects "Warn" it will initiate a warning alarm.
When the controller does not detect synchronization signal within the
pre-set synchronization time, it will initiate a warning alarm.
When the controller detects fewer modules on the MSC link than the
minimum number configured in the unit, it will initiate a warning alarm.
There are 2 possible reasons: a) Communication line between the
controllers disconnects, which interrupts communication.
b) Other parallel gen-sets controllers have not been powered on.
When the controller detects that the genset negative reactive power has
exceeded the pre-set value, it will initiate a warning alarm.
Table 9 Shutdown Alarm
When the controller detects an emergency stop alarm signal, it will initiate
a shutdown alarm.
When the controller detects that the generator speed has exceeded the
pre-set value, it will initiate a shutdown alarm.
When the controller detects that the generator speed has fallen below the
pre-set value, it will initiate a shutdown alarm.
When the controller detects that the engine speed is 0 and the action
selects "Shutdown", it will initiate a shutdown alarm.
When the controller detects that the genset frequency has exceeded the
pre-set value, it will initiate a shutdown alarm.
When the controller detects that the genset frequency has fallen below the
pre-set value, it will initiate a shutdown alarm.
When the controller detects that the generator voltage has exceeded the
pre-set value, the controller will initiate a shutdown alarm.
When the controller detects that the genset voltage has fallen below the
pre-set value, it will initiate a shutdown alarm.
If the engine does not fire after the pre-set number of attempts, it will
initiate a shutdown alarm.
When the controller detects that the genset current has exceeded the
pre-set value and the action selects "Shutdown", it will initiate a shutdown
alarm.
Description
Description