6.2 SHUTDOWN ALARM

When controller detects shutdown alarm, it will disconnect Gens close signal and stop the generator
immediately.
No.
Type
1
Emergency Stop
2
Over Speed
3
Under Speed
4
Loss of Speed Signal
5
AC Over Frequency
6
AC Under Frequency
7
AC Over Voltage
8
AC Under Voltage
9
Fail to Start
10
AC Over Current
11
Maintenance Due
12
ECU Shutdown
ECU Com Fail
13
Shutdown
AC Reverse Power
14
Shutdown
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Table 9 - Shutdown Alarms
Action Range
Active always
Active always
Active from wait for load to
stop cooling
Active from start idle to
stop idle
Active always
Active from wait for load
to stop cooling
Active always
Active from wait for load to
stop cooling
Active after failed to start
Active always
Active when maintenance
time is due
Active
when
controller
receives
ECU
indicator alarm
Active
when
controller
failed to comm. with ECU
Active always
2020-02-20
When controller detects emergency stop
signals, it will send stop signals.
When controller detects the speed value is
higher than the set value, it will send stop
signals.
When controller detects the speed value is
lower than the set value, it will send stop
signals.
When controller detects speed value equals
to 0, and the action select ―Shutdown‖, it will
send stop signals
When controller detects the frequency value
of AC genset is higher than the set value, it
will send stop signals.
When controller detects the frequency value
of AC genset is lower than the set value, it
will send stop signals.
When controller detects the voltage value of
AC genset is higher than the set value, it will
send stop signals.
When controller detects the voltage value of
AC genset is lower than the set value, it will
send stop signals.
If genset start failure within setting of start
times, controller will send stop signals.
When controller detects the current value of
AC genset is higher than the set value, it will
send stop signals.
When count down time is 0 and the action
select ―Shutdown‖, it will send stop signals.
When controller receives engine shutdown
red
signals via J1939, controller send stop
signals.
After engine start, controller dos not receive
data signals, via J1939, controller send stop
signals.
When controller detects reverse power value
of AC genset (power is negative) is higher
Version 1.0
Description
Page 22 of 69