Shutdown Alarm - Smartgen HGM410DC User Manual

Genset controller
Table of Contents

Advertisement

22
Gen Over Volt
23
Gen Under Volt
24
Gen Over Freq
25
Gen Under Freq

5.2 SHUTDOWN ALARM

When controller detects shutdown alarm, it will send signal to open breaker and shuts down generator.
The alarm information will be displayed on LCD.
No
Items
1
Emergency Shutdown
2
High Temperature
3
Low Oil Pressure
4
Over Speed
5
Under Speed
6
Loss Of Speed Signal
7
Gen Over Voltage
8
Gen Under Voltage
9
Gen Over Current
HGM410DC Genset Controller
When the controller detects that generate voltage has exceeded the
pre-set value, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that generate voltage has fallen below the
pre-set value, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that generate frequency has exceeded the
pre-set value, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that generate frequency has fallen below the
pre-set value, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the emergency shutdown signal, it will
initiate a shutdown alarm and the corresponding alarm information will be
displayed on LCD.
When controller detects that the water/cylinder temperature has exceeded
the pre-set value, it will initiate a shutdown alarm and the corresponding
alarm information will be displayed on LCD.
When the controller detects that the oil pressure has fallen below the
pre-set value, it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the generator speed has exceeded the
pre-set value, it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the generator speed has fallen below the
pre-set value, it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the engine speed is 0 and the delay is
NOT 0, it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the genset voltage has exceeded the
pre-set value, it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the genset voltage has fallen below the
pre-set value, it will initiate a shutdown alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that the genset current has exceeded the
pre-set value and delay is not 0, it will initiate a shutdown alarm and the
2015-11-12
HGM410DC Genset Controller User Manual
Description
Version 1.0
Page 12 of 34