No.
Type
16
ECU Warn
17
Gen Loss of Phase
Gen Reverse Phase
18
Sequence
19
Switch Fail Warn
Temperature Sensor
20
Open Circuit
21
High Temperature
22
Low Temperature
Oil Pressure Open
23
Circuit
24
Low Oil Pressure
Level Sensor Open
25
Circuit
26
Low Fuel Level
Flexible Sensor 1 Open
27
Circuit
28
Flexible Sensor 1 High
29
Flexible Sensor 1 Low
Flexible Sensor 2 Open
30
Circuit
31
Flexible Sensor 2 High
32
Flexible Sensor 2 Low
33
Digital Input
34
Earth Fault
HGM9510 Genset Parallel Controller User Manual
If an error message is received from ECU via J1939, it will initiate a warning
alarm.
If loss of phase detection is enabled, When controller detects the generator
loss phase, it will initiate a warning alarm.
When the controller detects a phase rotation error, it will initiate a warning
alarm.
When the controller detects that the breaker close or open failure occurs,
and the action selects "Warn", it will initiate a warning alarm.
When the controller detects that the temperature sensor is open circuit and
the action selects "Warn", it will initiate a warning alarm.
When the controller detects that engine temperature has exceeded the
pre-set value, it will initiate a warning alarm.
When the controller detects that engine temperature has fallen below the
pre-set value, it will initiate a warning alarm.
When the controller detects that the oil pressure sensor is open circuit and
the action selects "Warn", it will initiate a warning alarm.
When the controller detects that the oil pressure has fallen below the
pre-set value, it will initiate a warning alarm.
When the controller detects that the level sensor is open circuit and the
action selects "Warn", it will initiate a warning alarm.
When the controller detects that the fuel level has fallen below the pre-set
value, it will initiate a warning alarm.
When the controller detects that the flexible sensor 1 is open circuit and
the action selects "Warn", it will initiate a warning alarm.
When the controller detects that the sensor 1 value has exceeded the
pre-set value, it will initiate a warning alarm.
When the controller detects that the sensor 1 value has fallen below the
pre-set value, it will initiate a warning alarm.
When the controller detects that the flexible sensor 2 is open circuit and
the action selects "Warn", it will initiate a warning alarm.
When the controller detects that the sensor 2 value has exceeded the
pre-set value, it will initiate a warning alarm.
When the controller detects that the sensor 2 value has fallen below the
pre-set value, it will initiate a warning alarm.
When digit input port is set as warning and the alarm is active, it will initiate
a warning alarm.
If earth fault detection is enabled, when the controller detects that the earth
fault current has exceeded the pre-set value and the action select "Warn", it
Description
Page 22 of 68