Smartgen HGM9510 User Manual page 24

Genset parallel (with genset) controller
Hide thumbs Also See for HGM9510:
Table of Contents

Advertisement

No.
Type
11
Maintenance Due
12
ECU Shutdown
13
ECU Fail
14
Reverse Power
15
Over Power
Temperature Sensor
16
Open Circuit
17
High Temperature
Oil Pressure Open
18
Circuit
19
Low Oil Pressure
Level Sensor Open
20
Circuit
Flexible Sensor 1 Open
21
Circuit
22
Flexible Sensor 1 High
23
Flexible Sensor 1 Low
Flexible Sensor 2 Open
24
Circuit
25
Flexible Sensor 2 High
26
Flexible Sensor 2 Low
27
Digital Input
HGM9510 Genset Parallel Controller User Manual
When count down time is 0 and the action selects "Shutdown", it will
initiate a shutdown alarm.
If an error message is received from ECU via J1939, it will initiate a
shutdown alarm.
If the module does not detect the ECU data, it will initiate a shutdown
alarm.
If reverse power detection is enabled, when the controller detects that the
reverse power value (power is negative) has fallen below the pre-set value
and the action selects "Shutdown", it will initiate a shutdown alarm.
If over power detection is enabled, when the controller detects that the
power value (power is positive) has exceeded the pre-set value and the
action selects "Shutdown", it will initiate a shutdown alarm.
When the controller detects that the temperature sensor is open circuit and
the action selects "Shutdown", it will initiate a shutdown alarm.
When the controller detects that engine temperature has exceeded the
pre-set value, it will initiate a shutdown alarm.
When the controller detects that the oil pressure sensor is open circuit and
the action selects "Shutdown", it will initiate a shutdown alarm.
When the controller detects that the oil pressure has fallen below the
pre-set value, it will initiate a shutdown alarm.
When the controller detects that the level sensor is open circuit and the
action selects "Shutdown", it will initiate a shutdown alarm.
When the controller detects that the flexible sensor 1 is open circuit and
the action selects "Shutdown", it will initiate a shutdown alarm.
When the controller detects that the sensor 1 value has exceeded the
pre-set value, it will initiate a shutdown alarm.
When the controller detects that the sensor 1 value has fallen below the
pre-set value, it will initiate a shutdown alarm.
When the controller detects that the flexible sensor 2 is open circuit and
the action selects "Shutdown", it will initiate a shutdown alarm.
When the controller detects that the sensor 2 value has exceeded the
pre-set value, it will initiate a shutdown alarm.
When the controller detects that the sensor 2 value has fallen below the
pre-set value, it will initiate a shutdown alarm.
When digit input port is set as shutdown and the alarm is active, it will
initiate a shutdown alarm.
Description
Page 24 of 68