Smartgen HGM6100N Series User Manual

Smartgen HGM6100N Series User Manual

Genset controller
Hide thumbs Also See for HGM6100N Series:

Advertisement

HGM6100N SERIES
(HGM6110N/6120N/6110NC/6120NC/6110CAN/6120CAN)
GENSET CONTROLLER
USER MANUAL
SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Smartgen HGM6100N Series

  • Page 1 HGM6100N SERIES (HGM6110N/6120N/6110NC/6120NC/6110CAN/6120CAN) GENSET CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.
  • Page 2: Specification

    HGM6100N Series Genset Controller User Manual 3 SPECIFICATION Table 2 – Technical Parameters Items Contents Working Voltage DC8.0V to DC35.0V, continuous <3W(Standby mode: ≤2W) Power Consumption AC System 3P4W AC15V - AC360 V (ph-N) 3P3W AC30V - AC620 V (ph-ph)
  • Page 3 HGM6100N Series Genset Controller User Manual 4 OPERATION 4.1 KEYS DSCRIPTION Table 3 – Keys Description Icon Function Description Can stop generator under Manual/Auto mode; Can reset shutdown alarm; Press this key at least 3 seconds to test panel indicators are OK or Stop/ Reset not(lamp test);...
  • Page 4: Controller Panel

    HGM6100N Series Genset Controller User Manual 4.2 CONTROLLER PANEL Fig.1 - HGM6110N/ HGM6110NC/ HGM6110CAN Front Panel Indication Fig.2 - HGM6120N/ HGM6120NC/ HGM6120CAN Front Panel Indication Note: Partial indicator states: Alarm Lamp: slowly blink when warning alarms; fast blink when shutdown alarms; won’t illuminate when there is no alarm.
  • Page 5: Automatic Start/Stop Operation

    HGM6100N Series Genset Controller User Manual 4.3 AUTOMATIC START/STOP OPERATION Auto mode is activated by pressing the , LED indicator beside the button is illuminating which confirms this action. Starting Sequence HGM6120: When mains is abnormal (over/under voltage, lack of phase), enter into ―Mains Abnormal Delay‖...
  • Page 6: Emergency Start

    HGM6100N Series Genset Controller User Manual high speed running. If there is high temperature, low oil pressure, over speed and abnormal voltage during genset running, controller can protect genset to stop (detail procedures please refer to No.4~9 of Auto start operation). Under Manual Mode, switch won’t transfer automatically, it is necessary to press to transfer load.
  • Page 7 HGM6100N Series Genset Controller User Manual 6 CONNECTIONS Compared with HGM6120, HGM6110 doesn’t have 3-phase input terminal of mains voltage. The back panel of HGM6120 is as below. Fig.3 – Controller Rare Panel Drawing Table 6 – Terminal Connection Description...
  • Page 8 — When mains abnormal again, genset will start automatically and into normal running, send signal to make gens close, transfer ATS and make genset take load. If it not likes this, please check connections of ATS according to this manual. — If there are any other questions, please contact SmartGen’s service. HGM6100N Genset Controller 2019-03-28 Version 1.5...
  • Page 9: Typical Application

    HGM6100N Series Genset Controller User Manual 11 TYPICAL APPLICATION Fig.5 - HGM6110NC Typical Application Diagram Fig.6 - HGM6120NC Typical Application Diagram HGM6100N Genset Controller 2019-03-28 Version 1.5 Page 30 of 42...
  • Page 10 HGM6100N Series Genset Controller User Manual Fig.7 - HGM6110CAN Typical Application Diagram Fig.8 - HGM6120CAN Typical Application Diagram HGM6100N Genset Controller 2019-03-28 Version 1.5 Page 31 of 42...
  • Page 11: Overall Dimension And Panel Cutout

    HGM6100N Series Genset Controller User Manual Fig. 9 - Single Phase 2 Wire Fig. 10 - 2 Phase 3 Wire Note: Recommend that the output of crank and Fuel expand high capacity relay. 12 INSTALLATION 12.1 FIXING CLIPS The module is held into the panel fascia using the supplied fixing clips.

This manual is also suitable for:

Hgm6110nHgm6120nHgm6110ncHgm6120ncHgm6110canHgm6120can

Table of Contents