6.2 SHUTDOWN ALARM

When controller detects shutdown alarm, it will send signal to open breaker and shuts down
generator.
Shutdown alarms as following:
No.
Type
1
Emergency Stop
2
Over Speed
3
Under Speed
4
Loss of Speed Signal
5
Fail To Start
6
Gen Over Current
7
Maintenance Due
8
ECU Shutdown
9
ECU Com Fail
10
Aux High Temp
11
Aux Low OP
Temperature Sensor
12
Open Circuit
13
High Temperature
Oil Pressure Open
14
Circuit
15
Low Oil Pressure
HGM7110DC Genset Controller
When the controller detects an emergency stop alarm signal,
it will initiate a shutdown alarm.
When the controller detects that the generator speed has
exceeded the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the generator speed has
fallen below the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the generator speed is 0 and
the action select "Shutdown", it will initiate a shutdown alarm.
If the engine does not fire after the pre-set number of
attempts, it will initiate a shutdown alarm.
When the controller detects that the genset current has
exceeded the pre-set value and the action select "Shutdown",
it will initiate a shutdown alarm.
When count down time is 0 and the action select "Shutdown",
it will initiate a shutdown alarm.
If an error message is received from ECU via J1939, it will
initiate a shutdown alarm.
If an error message is NOT received from ECU via J1939, it
will initiate a shutdown alarm.
The controller will initiate a shutdown alarm if the input is
active.
The controller will initiate a shutdown alarm if the input is
active.
When the controller detects that the temperature sensor is
open circuit and the action select "Shutdown", it will initiate a
shutdown alarm.
When the controller detects that engine temperature has
exceeded the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the oil pressure sensor is
open circuit and the action select "Shutdown", it will initiate a
shutdown alarm.
When the controller detects that the oil pressure has fallen
below the pre-set value, it will initiate a shutdown alarm.
Version: 1.0
HGM7110DC Genset Controller
Description
2014-09-27
Page 24 of 68