Smartgen HGM9510 User Manual page 39

Genset parallel (with genset) controller
Hide thumbs Also See for HGM9510:
Table of Contents

Advertisement

No.
Items
2
Output Reverse
3
Action
4
Center Voltage SW1
Voltage
5
SW2
6
Sync Gain
7
Sync Stability
8
Load Gain
9
Load Stability
Mains Split Setting
1
AC System
2
Rated Voltage
Mains Rated
3
Frequency
4
Volt. Trans.(PT)
5
Mains Over Voltage
6
Mains Under Voltage
Mains
7
Frequency
Mains
8
Frequency
9
ROCOF
10
Vector Shift
NOTE: overcurrent setting details about DMT and IDMT.
DMT: overcurrent delay is definite time delay. Different overcurrent value has corresponding delay.
IDMT: overcurrent delay decrease with the increase of overcurrent. Different overcurrent value has corresponding delay.
IDMT formula:
T = t / ((IA/IT)-1)
2
HGM9510 Genset Parallel Controller User Manual
Parameters
(0-1)
(0-2)
(0-10.0)
Range
(0-10.0)
(0-500)
(0-2000)
(0-500)
(0-2000)
(0~3)
(30~30000)V
(10.0~75.0)Hz
(0-1)
(0-200)%
(0-200)%
Over
(0-200)%
Under
(0-200)%
(0-1.00)Hz/s
(0-20.0)°
Defaults
0
0: Disable; 1: Enable.
0: None; 1: Adjust to Rated Frequency;
1
2: Adjust to Center Point
0
Default central voltage: 0V.
2.0
Default volt. range: (-2.5~+2.5)V
20
Adjust and control before paralleling.
20
Adjust and control before paralleling.
20
Adjust and control after paralleling.
20
Adjust and control after paralleling.
0: 3P4W; 1: 3P3W;
0
2: 2P3W; 3: 1P2W.
To offer standards for detecting of mains'
over/under voltage and loading voltage. (It is
primary
230
transformer; it is line voltage when AC system
is 3P3W while it is phase voltage when using
other AC system).
To
offer
50.0
over/under/load frequency.
0
0: Disable ;
105%
Setting value is percentage of mains rated
volt. Delay value (default: 0.1s) and
95%
action (default: trip and stop) also can be set.
Setting value is mains rated frequency's
105%
percentage. Delay value (default: 0.1s) and
alarm action (default: trip and stop) also can
95%
be set.
Setting value is mains' rate of change of
frequency, and alarm action (default: trip and
0.20
stop) and delay value (default: 0.1s) also can
be set.
Setting value is phase angle's change rate of
mains voltage waveform, and alarm action
6.0
(default: trip and stop) and delay value
(default: 0.1s) also can be set.
Description
voltage
when
using
standards
for
detecting
1: Enable
Page 39 of 68
voltage
of
alarm

Advertisement

Table of Contents
loading