Smartgen HGM9510 User Manual page 34

Genset parallel (with genset) controller
Hide thumbs Also See for HGM9510:
Table of Contents

Advertisement

No.
Items
13
Under Volt. Warn
14
Over Freq. Warn
15
Under Freq. Warn
16
Loss of Phase
Phase
Sequence
17
Wrong
Generator Load Setting
1
Current Trans.
2
Full Current Rating
3
Full kW rating
4
Over Current
5
Over Power
6
Reverse Power
7
Earth Fault
Negative
Sequence
8
Current
9
Loss of Excitation
Switch Setting
1
Close Time
2
Open Time
Module Setting
1
Power On Mode
HGM9510 Genset Parallel Controller User Manual
Parameters
Defaults
(0~200)%
84%
(0~200)%
110%
(0~200)%
84%
(0~1)
1
(0~1)
1
(5~6000)/5
500
(5~6000)A
500
(0-20000)kW
276
(0~200)%
120%
(0~200)%
110%
(0~200)%
10%
(0~1)
0
(0~1)
0
(0~200)%
20%
(0~20.0)s
5.0
(0~20.0)s
3.0
(0~2)
0
Description
Delay value (default: 5s) and return value (default:
108%) can be set.
Setting value is percentage of generator rated
volt. Delay value (default: 5s) and return value
(default: 86%) also can be set.
Setting value is percentage of gens rated freq.
Delay value (default: 5s) and return value
(default: 108%) also can be set.
Setting value is percentage of gens rated freq.
Delay value (default: 5s) and return value
(default: 86%) also can be set.
0: Disable 1: Enable
The ratio of external CT.
Generator's rated current, standard of load
current.
Generator's full-load active power, standard of
load power.
Setting value is percentage of generator rated
current. Delay value can be set as DMT or
IDMT. Details please refer to DMT or IDMT
setting description.
Setting value is percentage of generator rated
active power. Delay value (default: 30s) and
action (default: trip and stop) can be set.
Setting value is percentage of generator rated
active power. Delay value (default: 10s) and
action (default: trip and stop) can be set.
0: Disable
1: Enable.
0: Disable
1: Enable.
Setting value is percentage of generator rated
reactive power. Delay value (default: 5s) and
action (default: trip) can be set.
Pulse width of mains/generator switch on.
When it is 0, means output constantly.
Pulse width of mains/ generator switch off.
0: Stop mode
1: Manual mode
2: Auto mode
Page 34 of 68