Protection; Warning - Smartgen HGM9510 User Manual

Genset parallel (with genset) controller
Hide thumbs Also See for HGM9510:
Table of Contents

Advertisement

6

PROTECTION

6.1 WARNING

When controller detects warning signals, it only sends warning but not shuts down generator.
No.
Type
1
Over Speed
2
Under Speed
3
Loss of Speed Signal
4
Gen Over Frequency
5
Gen Under Frequency
6
Gen Over Voltage
7
Gen Under Voltage
8
Gen Over Current
9
Fail To Stop
Charge Alternator
10
Failure
11
Battery Under Volt
12
Battery Over Volt
13
Maintenance Due
14
Reverse Power
15
Over Power
HGM9510 Genset Parallel Controller User Manual
Table 8 Warning Alarm
When the controller detects that the genset speed has exceeded the
pre-set value, it will initiate a warning alarm.
When the controller detects that the genset speed has fallen below the
pre-set value, it will initiate a warning alarm.
When the controller detects that the genset speed is 0 and the action
select "Warn", it will initiate a warning alarm.
When the controller detects that the genset frequency has exceeded the
pre-set value, it will initiate a warning alarm.
When the controller detects that the genset frequency has fallen below the
pre-set value, it will initiate a warning alarm.
When the controller detects that the generator voltage has exceeded the
pre-set value, the controller will initiate a warning alarm.
When the controller detects that the genset voltage has fallen below the
pre-set value, it will initiate a warning alarm.
When the controller detects that the genset current has exceeded the
pre-set value and the action selects "Warn", it will initiate a warning alarm.
After "fail to stop" delay, if gen-set does not stop completely, it will initiate a
warning alarm.
When the controller detects that charger voltage has fallen below the
pre-set value, it will initiate a warning alarm.
When the controller detects that start battery voltage has fallen below the
pre-set value, it will initiate a warning alarm.
When the controller detects that start battery voltage has exceeded the
pre-set value, it will initiate a warning alarm.
When count down time is 0 and the action selects "Warn", it will initiate a
warning alarm.
If reverse power detection is enabled, when the controller detects that the
reverse power value (power is negative) has fallen below the pre-set value
and the action selects "Warn", it will initiate a warning alarm.
If over power detection is enabled, when the controller detects that the
power value (power is positive) has exceeded the pre-set value and the
action selects "Warn", it will initiate a warning alarm.
Description
Page 21 of 68