8

SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

8.1 CONTENTS AND SCOPES OF PARAMETERS

No.
Items
Timer Setting
1
Start Delay
2
Stop Delay
3
Preheat Delay
4
Cranking Time
5
Crank Rest Time
6
Safety On Delay
7
Start Idle Time
8
Warming Up Time
9
Cooling Time
10
Stop Idle Time
11
ETS Solenoid Hold
12
Fail to Stop Delay
13
After Stop Time
Gas Engine Timers
14
Enable
15
Choke On Time
16
Gas On Delay
17
Ignition Off Delay
Engine Setting
1
Engine Type
HGM9510 Genset Parallel Controller User Manual
Table 13 Contents and Scopes of Parameters
Parameters
Defaults
(0~3600)s
5
(0~3600)s
30
(0~3600)s
0
(3~60)s
8
(3~60)s
10
(0-3600)s
10
(0~3600)s
10
(0~3600)s
30
(0~3600)s
60
(0~3600)s
10
(0~3600)s
20
(0~3600)s
0
(0~3600)s
0
(0-1)
0
(0-60)s
0
(0-60)s
0
(0-60)s
0
(0~39)
0
Description
Time from mains abnormal or remote start
signal is active to start genset.
Time from mains normal or remote start
signal is inactive to stop genset.
Time of pre-powering heat plug before starter
is powered up.
Time of starter power on.
The waiting time before second power up
when engine start fail.
Alarms for low oil pressure, high temperature,
under speed, under frequency/voltage, charge
fail are inactive.
Idle running time of genset when starting.
Warming up time between genset switch on
and high speed running.
Radiating time before genset stop, after it
unloads.
Idle running time when genset stop.
Stop electromagnet's power on time when
genset is stopping.
Time between ending of genset idle delay and
stopped when "ETS output time" is set as 0;
Time between ending of ETS hold delay and
stopped when "ETS output time" is not 0.
Time between genset stopped and standby.
0: Enable
1: Disable
When gas engine timer enabled, fuel oil
output is used for controlling gas valve.
Gas choke on control output time when start
engine.
When engine started, it starts to output after
the preset time delay.
When gas valve closed, it stop to output after
the preset delay.
Default: Conventional Engine (not J1939)
When connected to J1939 engine, choose the