5.2 SHUTDOWN ALARM

When controller detects shutdown alarm, it will send signal to stop the generator.
Shutdown alarms as following,
No.
Type
1
Emergency Stop
2
Over Speed
3
Under Speed
Loss Of Speed
4
Signal
5
Over Frequency
6
Under Frequency
7
Over Voltage
8
Under Voltage
9
Fail To Start
10
Over Current
11
Maintenance Due
Reverse Power
12
Shutdown
Over Power
13
Shutdown
14
Temp. Sensor Open
High Temp.
15
Shutdown
Pressure Sensor
16
Open
17
Low OP Shutdown
Level Sensor
18
Open
Oil
Temperature
19
Sensor Open
HGM9120 Genset Controller
HGM9120 Genset Controller
When controller detects emergency stop signal, it will send a
stop signal.
When controller detects the speed value is higher than the
set value, it will send a stop signal.
When controller detects the speed value is lower than the set
value, it will send a stop signal.
When controller detects speed value equals to 0, and the
action select "Shutdown", it will send a stop alarm signal
When controller detects the frequency value is higher than
the set value, it will send a stop signal.
When controller detects the frequency value is lower than
the set value, it will send a stop signal.
When controller detects the voltage value is higher than the
set value, it will send a stop signal.
When controller detects the voltage value is lower than the
set value, it will send a stop signal.
If genset start fail within setting of start times, controller will
send a stop signal.
When controller detects the current value is higher than the
set value, it will send a stop signal.
When count down time is 0 and the action select
"Shutsown", it will send a stop alarm signal.
When controller detects reverse power value (power is
negative) is lower than the set value, and the reverse power
action select "shutdown", it will send a stop alarm signal.
When controller detects reverse power value (power is
positive) is higher than the set value, and the reverse power
action select "shutdown", it will send a stop signal.
When controller detects sensor is open circuit, and the action
select "shutdown", it will send a stop signal.
When controller detects temperature is higher than the set
value, it will send a stop signal.
When controller detects sensor is open circuit, and the action
select "shutdown", it will send a stop signal.
When controller detects oil pressure is lower than the set
value, it will send a stop signal.
When controller detects sensor is open circuit, and the action
select "shutdown", it will send a stop signal.
When controller detects the sensor is open circuit, and the
action select "warn", it will send warn signal.