Smartgen HGM9510 User Manual page 41

Genset parallel (with genset) controller
Hide thumbs Also See for HGM9510:
Table of Contents

Advertisement

No.
23
Oil Pre-supply Output
24
Generator Excite
25
Pre-Lubricate
26
Remote Control Output
27
Reserved
28
Reserved
29
Close Gen Output
30
Open Gen Output
31
Reserved
32
Reserved
33
Start Relay
34
Fuel Relay
35
Idle Control
36
Speed Raise Relay
37
Speed Drop Relay
38
Energize to Stop
39
Speed Drop Pulse
40
ECU Stop
41
ECU Power Supply
42
Speed Raise Pulse
43
Crank Success
44
Generator OK
45
Generator Load Available
46
Reserved
47
Synchronizing
48
Common Alarm
49
Common Trip and Stop
50
Common Shutdown
51
Common Trip
52
Common Warn
53
Reserved
54
Battery Over Voltage
55
Battery Under Voltage
56
Charge Alternator Failure
57
Reserved
HGM9510 Genset Parallel Controller User Manual
Type
threshold.
Action from "crank on" to "safety on".
Output in start period. If there is no generator frequency during
hi-speed running, output for 2 seconds again.
Actions in period of pre-heating to safety run.
This port is controlled by communication (PC).
Control generator to take load.
Control generator to off load.
Action when genset is starting and disconnect when stop is
completed. When gas timer enabled, fuel oil relay output is used
for controlling gas valve.
Used for engine which has idles. Close before starting and open in
warming up delay; Close during stopping idle mode and open
when stop is completed.
Action in warming up delay.
Action between the period from "stop idle" to "failed to stop".
Used for engines with ETS electromagnet. Close when stop idle is
over and open when pre-set "ETS delay" is over.
Active 0.1s when controller enter into stop idle, used for control
part of ECU dropping to idle speed.
Used for ECU engine and control its stop.
Used for ECU engine and control its power.
Active 0.1s when controller enter into warming up delay; used for
control part of ECU raising to normal speed.
Close when detects a successful start signal.
Action when generator is normal.
Action in period of generator ok to hi-speed cooling.
Action when controller is synchronizing.
Action when genset common warning, common shutdown,
common trips alarm.
Action when common trip and stop alarm occur.
Action when common shutdown alarm occurs.
Action when common trips alarm occurs.
Action when common warning alarm occurs.
Action when battery over voltage warning alarm occurs.
Action when battery low voltage warning alarm occurs.
Action when charge fail warning alarms.