Advertisement

5.2 SHUTDOWN ALARM

When controller detects shutdown alarm, it will send signal to open breaker and stop the unit.
Shutdown alarm must be cleared manually and the fault removed to reset the module.
No.
Type
1
Emergency Stop
2
Over Speed
3
Under Speed
4
Loss of Speed Signal
5
Maintenance Due
6
ECU Shutdown
7
ECU Fail
Temperature
8
Open Circuit
9
High Temperature
Oil
Pressure
10
Circuit
11
Low Oil Pressure
Level
Sensor
12
Circuit
Flexible Sensor 1~6
13
Open
Flexible Sensor 1~6
16
High
Flexible Sensor 1~6
17
Low
APC715 Pump Unit Controller User Manual
Table 8 Shutdown Alarm
When the controller detects an emergency stop alarm signal, it
will initiate a shutdown alarm.
When the controller detects that the generator speed has
exceeded the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the generator speed has
fallen below the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the engine speed is 0 and the
action selects "Shutdown", it will initiate a shutdown alarm.
When maintenance countdown time is 0 and the action selects
"Shutdown", it will initiate a shutdown alarm.
If shutdown alarm signal is received from ECU via J1939, it will
initiate a shutdown alarm.
If the module does not detect the J1939 data, it will initiate a
shutdown alarm.
When the controller detects that the temperature sensor is
Sensor
open circuit and the action selects "Shutdown", it will initiate a
shutdown alarm.
When the controller detects that engine temperature has
exceeded the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the oil pressure sensor is
Open
open circuit and the action selects "Shutdown", it will initiate a
shutdown alarm.
When the controller detects that the oil pressure has fallen
below the pre-set value, it will initiate a shutdown alarm.
Open
When the controller detects that the sensor is open circuit and
the action selects "Shutdown", it will initiate a shutdown alarm.
When the controller detects that the sensor is open circuit and
the action selects "Shutdown", it will initiate a shutdown alarm.
When the controller detects the sensor value is higher than the
max. set value, it will initiate a shutdown alarm.
When the controller detects the sensor value is lower than the
min. set value, it will initiate a shutdown alarm.
Description
Page 22 of 62