6.2

SHUTDOWN ALARM

When controller detects shutdown alarm, it will send gen close signals and stop the generator.
No.
Type
1
Emergency Stop
2
Over Speed
3
Under Speed
4
Loss of Speed Signal
5
Over Frequency
6
Under Frequency
7
Over Voltage
8
Under Voltage
9
Fail To Start
10
Over Current
11
Maintenance Due
12
ECU Shutdown
13
ECU Comm. Fail
14
Reverse Power
15
Over Power
16
Temp. Sensor Open
17
High Temp.
HGM8100N Genset Controller User Manual
Table 9 Shutdown Alarms
When controller detects emergency stop signals, it will send stop
signals.
When controller detects the speed value is higher than the set
value, it will send stop signals.
When controller detects the speed value is lower than the set
value, it will send stop signals.
When controller detects speed value equals to 0, and the action
selects "Shutdown", it will send stop signals
When controller detects the frequency value is higher than the set
value, it will send stop signals.
When controller detects the frequency value is lower than the set
value, it will send stop signals.
When controller detects the voltage value is higher than the set
value, it will send stop signals.
When controller detects the voltage value is lower than the set
value, it will send stop signals.
If genset start failure within setting of start times, controller will
send stop signals.
When controller detects the current value is higher than the set
value, it will send stop signals.
When count down time is 0 and the action selects "Shutdown", it
will send stop signals.
When controller receives engine shutdown signals via J1939,
controller send stop signals.
After engine start, controller dos not receive data signals, via
J1939, controller send stop signals.
When controller detects reverse power value (power is negative)
is higher than the set value, and the reverse power action selects
"shutdown", it will send stop signals.
When controller detects power value (power is positive) is higher
than the set value, and the reverse power action selects
"shutdown", it will send stop signals.
When controller detects sensor is open circuit, and the action
selects "shutdown", it will send stop signals.
When controller detects temperature is higher than the set value,
Description
Page 22 of 66