Smartgen HGM9510 User Manual page 32

Genset parallel (with genset) controller
Hide thumbs Also See for HGM9510:
Table of Contents

Advertisement

No.
Items
2
Flywheel Teeth
3
Rated Speed
4
Loading Speed
5
Loss of Speed Signal
Loss of Speed Signal
6
Action
Over
7
Shutdown
Under
8
Shutdown
9
Over Speed Warn
10
Under Speed Warn
11
Battery Rated Voltage
12
Battery Over Volts
13
Battery Under Volts
14
Charge Alt Fail
15
Start Attempts
16
Crank Disconnect
HGM9510 Genset Parallel Controller User Manual
Parameters
(10~300)
(0~6000)RPM
(0~100)%
(0~3600)s
(0~1)
Speed
(0~200)%
Speed
(0~200)%
(0~200)%
(0~200)%
(0~60.0)V
(0~200)%
(0~200)%
(0~60.0)V
(1~10)times
(0~6)
Defaults
corresponding type.
Tooth number of the engine, for judging of
starter separation conditions and inspecting
118
of
engine
instructions.
Offer standard to judge over/under/loading
1500
speed.
Setting value is percentage of rated speed.
Controller detects when it is ready to load. It
90%
won't switch on when speed is under loading
speed.
Time from detecting speed is 0 to confirm the
5
action.
0
0: Warn;
Setting value is percentage of rated speed
114%
and delay value (default: 2s) also can be set.
Setting value is percentage of rated speed and
80%
delay value (default: 3s) also can be set.
Setting value is percentage of rated speed, delay
110%
value (default: 5s) and return value (default:
108%) also can be set.
Setting value is percentage of rated speed, delay
86%
value (default: 5s) and return value (default:
90%) also can be set.
Standard for detecting of over/under voltage
24.0
of battery.
Setting value is percentage of rated voltage of
120%
battery, delay value (default: 60s) and return
value (default: 115%) also can be set.
Setting value is percentage of rated voltage of
85%
battery, delay value (default: 60s) and return
value (default: 90%) also can be set.
In normal running, when charger D+(WL)
voltage under this value, charge failure
8.0
alarms. Delay value (default: 10s) and return
value (default: 10.0V) also can be set.
Max. Crank times of crank attempts. When
3
reach this number, controller will send start
failure signal.
See table 17.
2
There are 3 conditions of disconnecting
starter with engine. Each condition can be
Description
speed.
See
the
1: Shutdown
Page 32 of 68
installation