No.
16
Reserved
17
Auto Mode Lock
18
Auto Mode Invalid
19
Static Parallel Mode
20
Black-start
21
Inhibit Alarm Stop
22
Aux Instrument Mode
23
Reserved
24
Reset Maintenance
25
Reserved
26
Aux. High Temp
27
Aux. Low OP
Remote Start
28
(On Load)
Remote Start
29
(Off Load)
30
Aux. Manual Start
Remote Start On Load
31
(On Demand)
32
Reserved
33
Simulate Stop key
34
Simulate Manual key
35
Reserved
36
Simulate Auto key
37
Simulate Start key
38
Simulate G-Load key
39
Simulate M-Load key
40
NEL Manual Trip
HGM9510 Genset Parallel Controller User Manual
Type
When input is active, controller enters into Auto mode; all the
keys except
When input is active, controller won't work under Auto mode.
All shutdown alarms are prohibited except emergence stop.
(Means battle mode)
All outputs are prohibited in this mode.
Controller will set maintenance time and date as default when
input is active.
Connected sensor digital input.
Connected sensor digital input.
In Auto mode, when input active, genset can be started and with
load after genset is OK; when input inactive, genset will stop
automatically.
In Auto mode, when input is active, genset can be started and
without load after genset is OK; when input is inactive, genset
will stop automatically.
In Manual mode, when input active, genset will start
automatically;
automatically
In Auto mode, when input active, all genset that need to be
paralleled will start according to the priority and calling other
generator according to the load.
An external button (not self-lock) can be connected and pressed
as simulate panel.
An external button (not self-lock) can be connected and pressed
as simulate panel.
This is simulate G-close key when HGM9510 controller is
applied.
This is simulate G-open key when HGM9510 controller is
applied.
An external button (not self-lock) can be connected. Details of
Description
key and simulate auto key input does not work.
when
input
are inactive.
inactive,
genset
will
Page 46 of 68
stop