Dip Switch Setting; Dip Switch Sw1; Dip Switch Sw2 - Simplex 2004 Series Operation Manual

Fire alarm control unit
Hide thumbs Also See for 2004 Series:
Table of Contents

Advertisement

8 DIP switch setting

8.1

DIP switch SW1

1.
IDC function type for Zone 1 can be set using DIP switches SW1-1 and SW1-2.
2.
IDC function type for Zone 2 can be set using DIP switches SW1-3 and SW1-4.
3.
IDC function type for Zone 3 can be set using DIP switches SW1-5 and SW1-6.
4.
IDC function type for Zone 4 can be set using DIP switches SW1-7 and SW1-8.
5.
See the following tables for switch setting.
SW1-1
SW1-2
SW1-3
0
0
0
0
1
0
1
0
1
1
1
1
Note: You can assign different function types to each zone using their respective DIP switches.
8.2

DIP switch SW2

1.
NAC function type for NAC 1 can be set using DIP switches SW2-1 and SW2-2.
2.
NAC coding pattern for NAC 1 can be set using DIP switches SW2-3, SW2-4 and SW2-5.
3.
Silence/ Reset Inhibit feature can be enable or disable using DIP switch SW2-6.
4.
Alarm Cutout Timer feature can be enable or disable using DIP switch SW2-7.
5.
NAC 1 can be enable or disable using DIP switch SW2-8.
6.
See the following tables for switch setting.
SW2-1
0
0
1
1
SW2-3
SW2-4
0
0
0
0
1
1
1
1
SW2-6
SW2-7
page 23
Table 16: DIP switch SW1 to SW8 settings
SW1-4
SW1-5
SW1-6
0
0
0
1
0
1
0
1
0
1
1
1
Table 17: DIP switch SW2-1 and SW2-2 settings
SW2-2
0
1
0
1
Table 18: DIP switch SW2-3, SW2-4 and SW2-5 settings
SW2-5
0
0
0
1
1
0
1
1
0
0
0
1
1
0
1
1
Table 19: DIP switch SW2-6 settings
0
1
Table 20: DIP switch SW2-7 settings
0
1
2004 Foundation Series Fire Alarm Control Unit Operation Guide
SW1-7
SW1-8
Description
0
0
IDC function type for all 4 zones: FIRE (Default)
0
1
IDC function type for all 4 zones: SUPV
1
0
IDC function type for all 4 zones: VSMOKE
1
1
IDC function type for all 4 zones: WSO
Description
NAC function type for NAC 1: QALERT (Default)
NAC function type for NAC 1: SSIG
NAC function type for NAC 1: RSIG
SPARE
Description
NAC coding pattern for NAC 1: Temporal (Default)
NAC coding pattern for NAC 1: Sync
NAC coding pattern for NAC 1: Steady
NAC coding pattern for NAC 1: 20 BPM
NAC coding pattern for NAC 1: 120 BPM
SPARE
SPARE
SPARE
Description
Silence/ Reset Inhibit feature is disabled (default)
Silence/ Reset Inhibit feature is enabled
Description
Alarm Cutout Timer feature is disabled (default)
Alarm Cutout Timer feature is enabled
579-1403 Rev A