Table 2-6 Power Input; Table 2-7 Power Input Terminal; Table 2-8 Maximum Power/Current Consumption - NF DP Series Instruction Manual

Programmable ac power source
Table of Contents

Advertisement

2. Preparation before Use
Voltage
range
Frequency
range
 About power input terminal
Power input
Single-phase
input
Three-phase
Screw
three-wire input
Three-phase
four-wire input
Note: DP105 and DP120 are not in DP series Type R. The power input of DP015 and DP030 is single-phase only.
 About power cable
Use a cable of sufficient ampacity for the maximum current consumption (see Table 2-8). A
protective grounding cable should have ampacity higher than or equal to the power cable. For the
optional power cable, see 7.5.
Maximum
Rated
power
output
consumption
1.5 kVA
2.25 kVA
3 kVA
4.50 kVA
4.5 kVA
6.75 kVA
6 kVA
9.00 kVA
7.5 kVA
11.25 kVA
9 kVA
13.50 kVA
10.5 kVA
15.75 kVA
12 kVA
18.00 kVA
Note: The power input of DP015 and DP030 is single-phase only.
18

Table 2-6 Power Input

Single-phase input
90 V to 250 V
50 Hz 2 Hz or 60 Hz 2 Hz

Table 2-7 Power Input Terminal

DP015, DP030

Table 2-8 Maximum Power/Current Consumption

Single-phase
90 V
25 A
50 A
75 A
Power input
Three-phase three-wire
input
170 V to 250 V
DP series and DP series Type R
DP045, DP060
DP075, DP090
M6
Maximum current consumption
Three-phase
Single-phase
three-wire
170 V
170 V
13 A
26 A
40 A
23 A
53 A
36 A
66 A
46 A
79 A
46 A
93 A
58 A
106 A
69 A
PROGRAMMABLE AC POWER SOURCE
Three-phase four-wire
input
323 V to 433 V
(phase voltage
187 V to 250 V)
DP105, DP120
M8
M6
M6
Three-phase
four-wire
323 V
(phase voltage: 187 V)
13 A
25 A
25 A
25 A
37 A
37 A