10. Specifications

10.11 Measurement Function

All accuracy of the measurement function is indicated for 23 °C5 °C.
View
Normal
Simple
Voltage *35
Effective value
(rms)
DC average
value (avg)
Peak value (pk)
(each of
max and min)
*35: The accuracy values are in the case that the output voltage is within voltage setting range, values
for power factor 1 in DP series, and values for power factor 1 in DP series Type R. In the
polyphase model, polyphase system, and polyphase output of the Multi-phase, this specification
is for the phase voltage and the DC average value display cannot be selected.
*36: The accuracy of the peak value is for a waveform of DC or sine wave.
Voltage (Line voltage. Only with the polyphase model, polyphase system, and polyphase output of
the Multi-phase model. Only with sine waveform output.)
Effective value
(rms)
*37
*37: The displayed value is the result of calculation with the phase voltage measured value and the
phase angle setting value regarding the output voltage waveform as a sine wave.
278
Displays almost all the measured and setting values excluding the harmonic current
measurement on one screen.
Enlarges and displays three items among all the measured values except the
harmonic current measurement.
Full scale
250.0 V / 500.0 V
Resolution
0.1 V
Accuracy
DC, 45 Hz to 65 Hz
(0.5 % of rdg + 0.3 V / 0.6 V)
40 Hz to 550 Hz
(0.7 % of rdg + 0.9 V / 1.8 V)
250.0 V / 500.0 V
Full scale
Resolution
0.1 V
Accuracy
DC
 (|0.5 % of rdg| + 0.3 V / 0.6 V)
250.0 V / 500.0 V
Full scale
Resolution
0.1 V
Accuracy
DC, 45 Hz to 65 Hz
 (|2 % of rdg| + 1 V / 2 V)
*36
Full scale
1P3W: 500.0 V / 1000.0 V
3P4W: 433.0 V / 866.0 V
Resolution
0.1 V
All models
All models
Polyphase model, Polyphase system,
Polyphase output of the Multi-phase model