Mailbox Messaging
User Manual
4.4.5 Mailbox Message: Set Slave Address
This command makes it possible to set the node address of a specified slave, if
the slave supports this feature.
Note: The message data size depends on the actual slave implementation. Range 0 to 240 bytes.
Parameter
Command Initiator
Command Name
Command Number
Fragmented
Extended Header Data
Command and Response Layout: Set Slave Address
Message ID
Message information
Command
Data size
Frame count
Frame number
Offset high
Offset low
Extended word 1
Extended word 2
Extended word 3
Extended word 4
Extended word 5
Extended word 6
Extended word 7
Extended word 8
Message Data byte 1
Message Data byte 2
Message Data byte 3
Message Data byte "n"
Page 98 of 225
Description
Application
SET SLAVE ADDRESS
0600h
No
Fault information may be returned in the header of the response.
Command
(ID)
4002h
0006h
(Size of data)
0001h
0001h
0000h
0000h
Current
New Slave
Slave Addr.
Address
Slave Ident Number
No_add_
Chg
-
-
-
-
Slave Data 1
Slave Data 2
Slave Data 3
...
...
Slave Data n
MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform
Response
(ID)
0002h
0006h
(Size of data)
0001h
0001h
0000h
0000h
Current
New Slave
Slave Addr.
Address
Slave Ident Number
-
No_add_
Chg
-
Error Code 1 Error Code 2
Error Code 3 Error Code 4
Return Code
Fault Information
Slave Data 1
Slave Data 2
Slave Data 3
...
Slave Data n
PROFIBUS DPV1 Master
Set Slave Address
No. of Slave Data bytes (n)
ProSoft Technology, Inc.
July 8, 2011
Need help?
Do you have a question about the inRax MVI69-PDPMV1 and is the answer not in the manual?