4.4.4 Mailbox Message: Get Slave Configuration

This command reads the actual configuration (identifier bytes) of a specified
slave.
Note: The response data size depends on the actual slave implementation. Range 6 to 244.
Parameter
Command Initiator
Command Name
Command Number
Fragmented
Extended Header Data
Command and Response Layout: Get Slave Configuration
Message ID
Acyclic Message Status
Command
Data size
Frame count
Frame number
Offset high
Offset low
Extended word 1
Extended word 2
Extended word 3
Extended word 4
Extended word 5
Extended word 6
Extended word 7
Extended word 8
Page 96 of 225
Description
Application
GET SLAVE CONFIGURATION
0500h
No
Fault information may be returned in the header of the response.
Command
(ID)
4002h
Word
0005h
0000h
0001h
0001h
0000h
0000h
Slave
Address
-
-
-
-
-
-
-
MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform
Response
(ID)
0002h
0005h
Get Slave Configuration
(Size of data)
Number of identifier bytes
(n)
0001h
0001h
0000h
0000h
Slave
Address
-
-
-
Error Code 1 Error Code 2
Error Code 3 Error Code 4
Return Code
Fault Information
Identifier byte 1
Response data word 1
Identifier byte 2
Response data word 2
Identifier byte 3
Response data word 3
...
...
Identifier byte n
Response data word n